Siemens 6AV6651-7KA01-3AA4 - S7-1200 + KTP400 Basic Starter Kit 6AV6651-7KA01-3AA4 Benutzerhandbuch

Produktcode
6AV6651-7KA01-3AA4
Seite von 364
Technical specifications 
 
A.6 BB 1297 battery board 
 
Easy Book 
310
 
Manual, 03/2014, A5E02486774-AF 
A.6 
BB 1297 battery board 
BB 1297 Battery Board 
Table A- 35  General specifications 
Technical data 
BB 1297 Battery 
Order number 
6ES7 297-0AX30-0XA0 
Dimensions W x H x D (mm) 
38 x 62 x 21 
Weight 
28 grams 
Hold up time real time clock 
Approximately 1 year 
Type of battery 
CR1025
1
 
"Maint" LED of the CPU 
Indicating a battery replacement is needed 
User program 
Application / system can evaluate battery status 
 
1
  Refer to the S7-1200 Programmable Controller System Manual, Chapter 2, Installation for information about installing 
the BB 1297 or replacing a battery in the BB. 
The BB 1297 Battery board is used for applications where the real time clock retention time 
is beyond one month. Features of the BB 1297 Battery board are shown below: 
●  Supports time of day clock during PLC power off. The S7-1200 CPU, in combination with 
the BB 1297 Battery board, supports the Time of Day clock retention during a power off 
period of the application for up to one year. 
●  Only one BB 1297 Battery board or other SB can be used at a time. 
●  Hot plugging / hot swapping is not allowed. The BB 1297 Battery board is only 
exchangeable or pluggable while the CPU is powered off. While the CPU is powered off, 
and the BB 1297 is removed to exchange the actual battery, the internal super cap will 
hold the time of day while the user replaces the battery. 
●  The CPU "Maint" LED indicates when a replacement battery is needed. 
●  The user program allows you to monitor or check on the status of the battery, and battery 
board and allows a user message to be displayed on an HMI or web server.