Technical specifications 
 
A.8 RTD and Thermocouple modules 
Easy Book 
Manual, 03/2014, A5E02486774-AF 
317
 
Table A- 46  Analog output representation for current (CPU 1215C and CPU 1217C) 
System 
Current output range 
Decimal 
Hexadecimal 
0 mA to 20 mA 
 
32767 
7FFF 
See note 1 
Overflow  
 
32512 
7F00 
See note 1 
32511 
7EFF 
23.52 mA 
Overshoot range 
27649 
6C01 
 
27648 
6C00 
20 mA 
Rated range 
20736 
5100 
15 mA 
34 
22 
12 mV 
0 mA 
Negative values   
Negative values are not 
supported 
 
 
  In an overflow condition, analog outputs will behave according to the device configuration properties settings. In the 
"Reaction to CPU STOP" parameter, select either: "Use substitute value" or "Keep last value".  
A.8 
RTD and Thermocouple modules 
The thermocouple (TC) modules (SB 1231 TC and SM 1231 TC) measure the value of 
voltage connected to the analog inputs. This value can be either temperature from a TC or 
volts. 
●  If voltage, the nominal range full scale value will be decimal 27648. 
●  If temperature, the value will be reported in degrees multiplied by ten (for example, 25.3 
degrees will be reported as decimal 253). 
The RTD modules (SB 1231 RTD and SM 1231 RTD) measure the value of resistance 
connected to the analog inputs. This value can be either temperature or resistance. 
●  If resistance, the nominal range full scale value will be decimal 27648. 
●  If temperature, the value will be reported in degrees multiplied by ten (for example, 25.3 
degrees will be reported as decimal 253). 
The RTD modules support measurements with 2-wire, 3-wire and 4-wire connections to the 
sensor resistor. 
 
 
Note 
The RTD and TC modules report 32767 on any activated channel with no sensor connected. 
If open wire detection is also enabled, the module flashes the appropriate red LEDs. 
Best accuracy will be achieved for the 10 Ω RTD ranges if 4 wire connections are used. 
The resistance of the connection wires in 2 wire mode will cause an error in the sensor 
reading, and therefore accuracy is not guaranteed.