Technical specifications 
 
A.8 RTD and Thermocouple modules 
Easy Book 
Manual, 03/2014, A5E02486774-AF 
327
 
Table A- 57  Resistance 
Range 
Under range 
minimum 
Nominal range 
low limit 
Nominal range 
high limit 
Over 
range 
maximum
1
 
Normal range 
accuracy 
@ 25 °C 
Normal range 
accuracy 
-20 °C to 60 °C 
150 Ω 
n/a 
0 (0 Ω) 
27648 (150 Ω)  176.383 Ω  ±0.05% 
±0.1% 
300 Ω 
n/a 
0 (0 Ω) 
27648 (300 Ω)  352.767 Ω  ±0.05% 
±0.1% 
600 Ω 
n/a 
0 (0 Ω) 
27648 (600 Ω)  705.534 Ω  ±0.05% 
±0.1% 
 
1
  Resistance values above the over-range maximum value are reported as 32767. 
A.8.8 
RTD filter selection and update times 
Table A- 58  Filter selection and update times 
Noise rejection 
frequency (Hz) 
Integration time 
(ms) 
Update time (seconds) 
1-channel SB 
4-channel SM 
8-channel SM 
10 
100 
4-/2-wire: 0.301 
3-wire: 0.601 
4-/2-wire: 1.222 
3-wire: 2.445 
4-/2-wire: 2.445 
3-wire: 4.845 
50 
20 
4-/2-wire: 0.061 
3-wire: 0.121 
4-/2-wire: 0.262 
3-wire: .505 
4-/2-wire: 0.525 
3-wire: 1.015 
60 
16.67 
4-/2-wire: 0.051 
3-wire: 0.101 
4-/2-wire: 0.222 
3-wire: 0.424 
4-/2-wire: 0.445 
3-wire: 0.845 
400
1
 
10 
4-/2-wire: 0.031 
3-wire: 0.061 
4-/2-wire: 0.142 
3-wire: 0.264 
4-/2-wire: 0.285 
3-wire: 0.525 
 
1
  To maintain module resolution and accuracy when the 400 Hz filter is selected, the integration time is 10 ms. This 
selection also rejects 100 Hz and 200 Hz noise. 
 
 
 
Note 
The module reports 32767 on any activated channel with no sensor connected. If open wire 
detection is also enabled, the module flashes the appropriate red LEDs. 
Best accuracy will be achieved for the 10 Ω RTD ranges if 4 wire connections are used. 
The resistance of the connection wires in 2 wire mode will cause an error in the sensor 
reading and therefore accuracy is not guaranteed.