Siemens 6AV6651-7KA01-3AA4 - S7-1200 + KTP400 Basic Starter Kit 6AV6651-7KA01-3AA4 Benutzerhandbuch

Produktcode
6AV6651-7KA01-3AA4
Seite von 364
Easy to create the device configuration 
 
5.7 Protecting access to the CPU or code block is easy 
 
Easy Book 
82
 
Manual, 03/2014, A5E02486774-AF 
5.7 
Protecting access to the CPU or code block is easy 
The CPU provides four levels of security for restricting access to specific functions. When 
you configure the security level and password for a CPU, you limit the functions and memory 
areas that can be accessed without entering a password.  
Each level allows certain functions to be accessible without a password. The default 
condition for the CPU is to have no restriction and no password-protection. To restrict access 
to a CPU, you configure the properties of the CPU and enter the password. 
Entering the password over a network does not compromise the password protection for the 
CPU. Password protection does not apply to the execution of user program instructions 
including communication functions. Entering the correct password provides access to all of 
the functions at that level. 
PLC-to-PLC communications (using communication instructions in the code blocks) are not 
restricted by the security level in the CPU.  
Table 5- 4 
Security levels for the CPU 
Security level 
Access restrictions 
Full access (no 
protection) 
Allows full access without password protection. 
Read access 
Allows HMI access and all forms of PLC-to-PLC communications without password protection. 
Password is required for modifying (writing to) the CPU and for changing the CPU mode 
(RUN/STOP). 
HMI access 
Allows HMI access and all forms of PLC-to-PLC communications without password protection. 
Password is required for reading the data in the CPU, for modifying (writing to) the CPU, and for 
changing the CPU mode (RUN/STOP). 
No access (complete 
protection) 
Allows no access without password protection.  
Password is required for HMI access, reading the data in the CPU, for modifying (writing to) the 
CPU, and for changing the CPU mode (RUN/STOP) 
Passwords are case-sensitive. To configure the protection level and passwords, follow these 
steps: 
1.  In the "Device configuration", select the CPU. 
2.  In the inspector window, select the "Properties" tab. 
3.  Select the "Protection" property to select the protection level and to enter passwords.