Finder Electricity meter (3-phase) digital 65 A MID-approved: No 7E.46.8.400.0002 7E.46.8.400.0002 Datenbogen
Produktcode
7E.46.8.400.0002
10/65
5/6
0.04
0.01
0.5...65
0.05...6
1,950 (10 ms)
180 (10 ms)
3 x 230
3 x 230
(0.8...1.15)U
N
(0.8...1.15)U
N
50/60
50/60
<
1.5
<
1.5
Seven digit counter, LCD with backlight
999,999.9/0.01 **
9,999,999/0.1 ***
100
10
5...30 5...30
20
20
10
10
1,000
10
30
30
100
100
1,000
1,000
1 / B
1 / B
–10…+55 °C
–10…+55 °C
II
II
IP 50/IP 20
IP 50/IP 20
2
Features
kWh Energy meter
3-phase with multi-functional LC-Display
3-phase with multi-functional LC-Display
Type 7E.46-0002 10(65)A - Single and Dual tariff
Type 7E.56-0000 5 (6)A - for current transformer
Type 7E.56-0000 5 (6)A - for current transformer
up to 1,500 A
•
Complies with EN 62053-21 and EN 50470
•
Display indicates total consumption, partial
consumption (this value is resettable),
instantaneous power per phase or all phases,
voltage per phase, current per phase
instantaneous power per phase or all phases,
voltage per phase, current per phase
•
ERROR-Display, in case of missing phase or
wrong current direction
•
Seven digit counter, LCD with backlight
•
Accuracy class: 1/B
•
Easy to operate by two control keys
•
LC-Display can be read twice within a period
of 10 days following the loss of supply voltage
•
Protection class II
•
Pulse output for remote energy management;
SO interface (open collector) according
DIN 43864 to link the energy meter to a
centrally located monitoring/management system
DIN 43864 to link the energy meter to a
centrally located monitoring/management system
•
Tamper-proof cover with lead seal facility
available as an accessory
•
35 mm rail (EN 60715) mount
•
MID compliant version (50 Hz only) available
•
Nominal current 10 A (65 A Maximum)
•
3-phase
•
Single and Dual tariff (Day and Night)
•
70 mm wide
•
Nominal current 5 A (6 A Maximum)
•
3-phase
•
Usable with current transformer up to 1,500 A
•
14 selectable Current Transformer ratios
•
70 mm wide
Specification
Nominal/Maximum current
A
Minimum measured current
A
Current range (within accuracy class)
A
Maximum peak current
A
Supply (& monitored) voltage (U
N
)
V AC
Operating range
Frequency
Hz
Power consumption per phase
W
Display (digit height 6 mm)
Max. totalising count/Min. increment
kWh
LCD-segment pulses per kWh
Open collector- output specification (SO+/SO–)
Voltage (external supply)
V DC
Maximum current
mA
Maximum leakage current @30 V/25 °C
μA
Pulses per kWh
Pulse length
ms
Internal series resistance
Ω
Maximum Cable length @30 V/20 mA
m
Technical data
Accuracy class
Ambient temperature
°C
Protective class
Protection category: Housing/terminals
Approvals (according to type)
* Current transformer ratios / F = 250 mA T
F
F
F
*
Current transformer ratios: 5:5, 50:5,
100:5, 150:5, 200:5, 250:5, 300:5,
400:5, 500:5, 600:5, 750:5, 1,000:5,
1,250:5, 1,500:5.
100:5, 150:5, 200:5, 250:5, 300:5,
400:5, 500:5, 600:5, 750:5, 1,000:5,
1,250:5, 1,500:5.
** 0.01 kWh for readings ≤ 99,999.99 kWh
and 0.1 kWh for readings ≥ 100,000.0 kWh
*** 0.1 kWh for readings ≤ 999,999.9 kWh
and 1 kWh for readings ≥ 1,000,000 kWh
For outline drawing see page 8
R
T1,T2
= Tariff switching equipment
7E Series - Energy meter
7E.46.8.400.00x2
7E.56.8.400.00x0
X-2012, www
.finder
net.com