Burnham Series C Power Flame Datenbogen

Seite von 2
Power Flame Burner Information
Burner Model
Motor
Firing Sequence
[1]
Standard UL Flame Safeguard
Gas Train
Horsepower
Boiler Size
Gas and 
Gas/#2 Oil
#2 Oil
Gas
#2 Oil and 
Gas/#2 Oil
Voltage
Gas
#2 Oil and 
Gas/#2 Oil
Gas
#2 Oil
Gas/#2 Oil
Size 
[4] [5]
Min. Pres. Max. Pres.
C-20
C1-*-10
C1-O
1/3
1/2
115/60/1
On-Off
On-Off
RM7897A/UV
R7184P/CC
RM7897C/UV
1
3.5" w.c. 
14.0" w.c.
C-30
C1-*-12
C1-O
1/2
1/2
115/60/1
On-Off
On-Off
RM7897A/UV
R7184P/CC
RM7897C/UV
1
1/4
5.5" w.c. 
14.0" w.c.
C-40
C2-*-15
C2-OA
1/2
3/4
230/60/1
[3]
On-Off
L-H-O
RM7897A/UV
R7184P/CC
RM7897C/UV
1
1/4
4.5" w.c. 
14.0" w.c.
C-50
C2-*-20A
C2-OA
3/4
3/4
 / 1 
[2]
230/60/1
L-H-O
L-H-O
RM7897A/UV
R7184P/CC
RM7897C/UV 1
1/2 / 
1
1/4
6.8" w.c. 
14.0" w.c.
C-60
C2-*-20B
C2-OB
1
1
1/2
230/60/1
L-H-O
L-H-O
RM7897A/UV
R7184P/CC
RM7897C/UV
2 / 1
1/2
5.2" w.c. 
14.0" w.c.
C-70
C2-*-20B
C2-OB
1
1
1/2
230/60/1
L-H-O
L-H-O
RM7897C/UV
R7184P/CC
RM7897C/UV
2 / 1
1/2
6.7" w.c. 
14.0" w.c.
C-80
C3-*-20
C3-O
1
1/2
2
208/460/3
L-H-O
L-H-O
RM7897C/UV RM7897C/UV RM7897C/UV
2 / 1
1/2
8.0" w.c. 
14.0" w.c.
C-90
C3-*-20
C3-O
1
1/2
2
208/460/3
L-H-O
L-H-O
RM7897C/UV RM7897C/UV RM7897C/UV
2
7.9" w.c. 
14.0" w.c.
C-100
C3-*-25B
C3-OB
3
3
208/460/3
L-H-O
L-H-O
RM7897C/UV RM7897C/UV RM7897C/UV
2
7.4" w.c. 
14.0" w.c.
C-125
C4-*-30
C4-OB
5
5
208/460/3
L-H-O
L-H-O
RM7897C/UV RM7897C/UV RM7897C/UV
2
10.5" w.c.
14.0" w.c.
C-150
C5-*-30
C5-O
7 1/2
7 1/2
208/460/3
MOD
MOD
RM7840L/UV RM7840L/UV RM7840L/UV
2 1/2
10.0" w.c.
28.0" w.c.
C-175
C5-*-30
C5-O
7 1/2
7 1/2
208/460/3
MOD
MOD
RM7840L/UV RM7840L/UV RM7840L/UV
3
10.9" w.c.
28.0" w.c.
C-200
C6-*-30
C6-O
10
10
208/460/3
MOD
MOD
RM7840L/UV RM7840L/UV RM7840L/UV
3
11.5" w.c.
28.0" w.c.
[1]  Explanation of Firing Sequences:
Gas and Gas Sequence on Combination Gas/Oil Boilers
On-Off
Slow opening gas valve, fixed air damper, diaphragm gas valve.
L-H-O
Slow opening gas valve, adjustable position (LFS) air damper, linked to motorized gas valve.
Oil and Oil Sequence on Combination Gas/Oil Boilers
On-Off
Fixed air damper, oil valve.
On-Off LFS Fixed air low fire start.
L-H-O
Adjustable air damper (spring close), linked to oil pressure cylinder, oil pressure regulator and by-pass valve for LFS.
[2]  Oil blower motor is 3/4 hp and combination gas/oil is 1 hp.
[3]  Voltage on gas burner model is 115/60/1.
[4]  Model C-50 & C-60 - Dual size gas trains:  Leak test cock and main gas valve are indicated by the first number; combination gas valve/regulator and main shutoff cock are 
      indicated by the second number.
[5]  Models C-70 & C-80 - Dual size gas trains:  Leak test cock, main gas valve and auxiliary gas valve are indicated by the first number; gas regulator and main shutoff cock are 
      indicated by the second number.
 8/10
C SERIES