Utica Boilers SSV Handbuch

Seite von 6
P/N 240010732 REV A, [07/2014]
Models & Capacities
Size
Boiler Input Rate (MBH)
(1)
Heating 
Capacity (MBH)
(1)(2)
Net AHRI
 Rating, Water 
(MBH)
(1)(3)
AFUE
(2)
Maximum
Minimum
SSV-050
50
10
46
40
95.0
SSV-075
75
15
69
60
95.0
SSV-100
100
20
91
79
95.0
SSV-150
150
30
139
121
95.0
SSV-200
200
40
185
161
95.0
*   SSV Models are ENERGY STAR rated products.
(1)
 1000 Btu/hr (British Thermal Units Per Hour)
(2)
 Heating Capacity and AFUE (Annual Fuel Utilization Efficiency) are based on DOE (Department of Energy) test  
procedures. 
(3) 
Net AHRI Ratings based on piping and pickup allowance of 1.15. Contact Technical Support before selecting boiler for installations 
having unusual piping and pickup requirements, such as intermittent system operation, extensive piping systems,  etc.
• Heat Exchanger Assembly
 
X
Vertically mounted single piece helical fin tube coil.  Manufactured out of 316L stainless 
steel tubing with 444 stainless steel fins welded onto the coil with a laser automated 
process.  ASME stamped  with a 150 psi maximum allowable  working pressure.  A 30psi 
safety relief valve is standard. 
 
X
Non-metallic flue gas collector.
• Electrical
 
X
User Interface relocation capable.
 
X
Line voltage junction box with DHW Pump, CH Pump and Primary Pump connections. 
 
X
Low voltage terminal strip. 
OPTIONAL EQUIPMENT:
• Floor mounting stand
• Multiple boiler system sensor
 
 
2201 Dwyer Ave.    Utica, NY 13501     www.UticaBoilers.com