HP Performance Optimized Data Center (POD) 40cp Installationsanleitung
Supported facility connections 20
The HP POD ECS offers:
•
The ability to monitor the status of water and air temperatures, water pressures, and water flow rates
•
Immediate notification of supported alarm messages
For additional points that can be monitored, see the I/O (Input/Output) Controls Points List.
Fire, safety, and security notifications
Dry contacts are provided to enable the connection between the fire alarm system and the central facility
fire detection system, relay alarm, and trouble conditions at each HP POD.
Your building fire, safety, and security system relays the following HP POD-initiated alarms, which operate
independently of each other.
fire detection system, relay alarm, and trouble conditions at each HP POD.
Your building fire, safety, and security system relays the following HP POD-initiated alarms, which operate
independently of each other.
Alarm
Meaning
Solution
Smoke alarm
Smoke has been detected in the HP
POD.
POD.
Activate the EPO. Follow standard
emergency procedures for your
facility.
emergency procedures for your
facility.
Security
A security breach has occurred.
Follow standard emergency
procedures for your facility.
procedures for your facility.
EPO
Someone has activated the EPO
system and shut down the HP POD.
system and shut down the HP POD.
Follow standard emergency
procedures for your facility.
procedures for your facility.
The electrical layout of the fire alarm system is as described in the schematic drawing that is supplied with
the HP POD.