Closed Loop Position Mode
88
AX1500 Motor Controller User’s Manual
 Version 1.9b. June 1, 2007
The diode polarity depends on the particular wiring and motor orientation used in the appli-
cation. If the diode is mounted backwards, the motor will not stop once the limit switch 
lever is pressed. If this is the case, reverse the diode polarity.
The diodes may be eliminated, but then it will not be possible for the controller to move the 
motor once either of the limit switches has been triggered.
The main benefit of this technique is its total independence on the controller’s electronics 
and its ability to work in practically all circumstances. Its main limitation is that the switch 
and diode must be capable of handling the current that flows through the motor. Note that 
the current will flow though the diode only for the short time needed for the motor to move 
away from the limit switches.
Another method uses the AX1500’s Emergency Stop input to shut down the controller if 
any of the limit switches is tripped. Figure 54 shows the wiring diagram used in this case. 
Each of the limit switches is a Normally Open switch. Two of these switches are typically 
required for each motor. Additional switches may be added as needed for the second 
motor and/or for a manual Emergency Stop. Since very low current flows through the 
switches, these can be small, low cost switches.
The principal restriction of this technique is that it depends on the controller to be fully 
functioning, and that once a switch is activated, the controller will remain inactive until the 
switch is released. In most situations, this will require manual intervention. Another limita-
tion is that both channels will be disabled even if only one channel caused the fault.
Motor
SW1
SW2
Controller
FIGURE 53. Safety limit switches interrupting power to motors