About this document 
This document outlines the site and preparation requirements for a 6 m (20 ft) HP POD 20c as it is being 
released internationally. The customer must provide a qualified architectural or consulting engineering team 
to generate site-specific documents for each HP POD 20c installation, including final site drawings. The 
customer site installation design must comply with all national, regional, and local regulations, ordinances, 
codes, and the specifications that are listed in this document. 
This guide is part of the core documentation for the HP POD 20c. The actual location of various components 
or included subsystems and their operation in your HP POD 20c might vary from what is described in this 
document. For information specific to your HP POD 20c, see the drawings that are included in the 
Operations and Maintenance Manual for the HP Performance Optimized Datacenter 20c, or contact HP. 
 
Safety and IEC compliance 
The HP POD 20c is examined, tested, and found to be in compliance with IEC/EN 60950 Part 1 and Part 
22 as an Information Technology Product. For more information, see "HP POD 20c regulatory compliance 
(on page 
).
The HP POD 20c is not suitable for long-term human occupancy. The HP POD 20c is Listed as a Product that 
provides service access areas for periodic maintenance and service. These areas must be used only by 
owner-authorized and qualified personnel who are trained in the maintenance and service of the HP POD 
20c components. 
   
 
IMPORTANT:
  Before installing the HP POD 20c, consult your local Authorities for applicable 
regulations and to review site-specific location guidelines. If needed, obtain any necessary 
permits. 
   
Additional considerations for safety and Electrical compliance are as follows: 
• 
The HP POD 20c is Certified as an Information Technology Product to IEC/EN 60950 Part 1 and Part 
22. 
• 
The HP POD 20c is evaluated as a "non-inhabitable product" that provides "service access" areas for 
customer-authorized, qualified, and trained service personnel. 
• 
The electrical connections of the HP POD 20c are evaluated as feeder connections for connection to an 
existing facility, and are not suitable as "service entrance" for connection to the utility. 
• 
The HP POD 20c is designed for stationary installation outdoors in a Pollution Degree 3 environment, 
in restricted access locations, with field wiring terminals provided for permanent supply connections. 
• 
The HP POD 20c meets the following ratings.  
 
Feature 
Specification 
Category 
Rated Overvoltage Category III 
Protection 
Surge protection device