White Rodgers 1F95-1280 Benutzerhandbuch

Seite von 16
Model
Programming Choices
1F95-1280
7 Day
5/1/1 Day
Non-Programmable
www.white-rodgers.com
Big Blue Commercial Universal Thermostat 
with Damper or Economizer Control and 
Automatic Heat/Cool Changeover Option
PART NO. 37-6978A
0832
Single Stage, Multi-Stage, Heat Pump
Installation and Operating Instructions
APPLICATIONS
1F95-1280 Commercial Touchscreen Thermostat
SPECIFICATIONS
Electrical Rating:
 
Battery Power . . . . . . . . . . . . . . . . . . . . . . . . . .    mV to 30 VAC, NEC Class II, 50/60 Hz or DC
 
Input-Hardwire  . . . . . . . . . . . . . . . . . . . . . . . . .    20 to 30 VAC
Terminal Load  . . . . . . . . . . . . . . . . . . . . . . . . . . . . .    1.5A per terminal, 2.5A maximum all terminals combined
Setpoint Range  . . . . . . . . . . . . . . . . . . . . . . . . . . . .    45 to 99°F (7 to 32°C)
Differential (Single Stage)  . . . . . . . . . . . . . . . . . . . .    Heat 0.6°F; Cool 1.2°F
Differential (Multi-Stage)  . . . . . . . . . . . . . . . . . . . . .    Heat 0.6°F; Cool 1.2°F
Differential (Heat Pump)  . . . . . . . . . . . . . . . . . . . . .    Heat 1.2°F; Cool 1.5°F
Operating Ambient. . . . . . . . . . . . . . . . . . . . . . . . . .    32°F to +105°F (0 to +41°C)
Operating Humidity  . . . . . . . . . . . . . . . . . . . . . . . . .    90% non-condensing max.
Shipping Temperature Range  . . . . . . . . . . . . . . . . .    -40 to +150°F (-40 to +65°C)
Dimensions Thermostat. . . . . . . . . . . . . . . . . . . . . .    4.6"H x 5.9"W x 1.2"D
To prevent electrical shock and/or equipment damage, 
disconnect electric power to system at main fuse or 
circuit breaker box until installation is complete.
CAUTION
!
Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS 
CAREFULLY BEFORE INSTALLING OR OPERATING THIS 
CONTROL COULD CAUSE PERSONAL INJURY AND/OR 
PROPERTY DAMAGE.
THERMOSTAT APPLICATION GUIDE
Thermostat 
Confi guration 
Options
Thermostat 
Applications
Maximum 
Stages
Heat/Cool
W/ Economizer
Max. Stage
Heat/Cool
Single Stage 1
No Heat Pump (SS1)
Gas, Oil, Electric, Heat Only, 
Cool Only or Heat/Cool 
Systems, 2 or 3 wire Hydronic 
Zone (Hot Water or Steam) 
Systems, 24 Volt or Millivolt
1/1
1/2
Multi Stage 2
No Heat Pump (MS2)
2/2
2/3
Heat Pump 1
Single Stage 
Compressor Heat 
Pump (HP1)
Single Stage Compressor Heat 
Pump Systems - up to 2 Stages 
Aux./Emergency Heat
3/1
3/2
Heat Pump 2
Two Stage or Two
Compressor Heat 
Pump (HP2)
Two Stage or Two Compressor 
Heat Pump systems - up to 2 
Stages Aux./Emergency Heat
4/2
4/3
ATTENTION: MERCURY NOTICE
This product does not contain mercury. However, this prod-
uct may replace a product that contains mercury.
Mercury and products containing mercury must not be 
discarded in household trash. Do not touch any spilled 
mercury. Wearing non-absorbent gloves, clean up any 
spilled mercury and place in a sealed container. For proper 
disposal of a product containing mercury or a sealed 
container of spilled mercury, place it in a suitable shipping 
container. Refer to www.white-rodgers.com for location to 
send the product containing mercury.
Index
Page
Installation
2
Wiring Diagrams
3
Thermostat Quick Reference
4
Installer Confi guration Menu
5
Operating Your Thermostat
9
Programming
10
Troubleshooting
14