Liebert MR1 Benutzerhandbuch

Seite von 19
 
Liebert MR1 
 3 
 
Section 2:  INSTALLATION 
 
Mounting 
The MR1 Mini-Remote is completely tested, then shipped from 
the factory disassembled for your convenience during 
installation.  To begin flush-mount installation, please refer to 
Figure 2A.  An optional 30-foot control cable can be supplied to 
allow the display to be located remotely from the electrical box.  
Refer to Figure 2b. 
The electric box containing the power supply is designed for 
flush-mounting into a finished interior wall.  A wall plate is 
supplied to cover the drywall opening, with the display mounted 
directly in front of the wall plate/electric box. 
1. Mount the electric box (Item 5) in the wall at a convenient 
location. 
2. Make each power and unit connection (to Item 4) by 
inserting bare wire end into compression terminal and 
tightening screw.  Refer to Electrical Connections section. 
If 30-foot cable is used, disconnect factory wire harness and 
attach cable to screw terminals per Figure 2. 
NOTE: Use minimum         
18 gauge wire for all 
customer interface wiring. 
3. Route control cable through wall plate and electric box 
cover, then connect to electrical box at TB1 (on Item 4). 
4. Attach electric box cover (Item 3) with two (2) screws. 
5. Remove the front cover from the MR1 display panel (Item 
1) by gently prying open at the slots on the top and bottom 
of the display. Attach the control panel rear plastic and the 
wall plate (Item 2) to the electric box with two (2) screws. 
6. Snap display panel front onto the rear plastic part. 
7. Apply power to the MR1. Operate the system to test status 
and alarm monitoring, and customer selected options 
including on/off control.  Also test optional customer 
interface (4 inputs and 1 output), if applicable. 
Call Liebert Environmental Support at 1-800-543-2778 if 
assistance is required for the installation or operation of the 
Mini-Remote.