Westinghouse EPA (49 state) and CARB (50 state) 10KPRO FULLY FEATURED Benutzeranleitung

Seite von 106
  
33
OPERATION
1
2
Figure 30 – Circuit Breakers – 8KPRO
1 -   120V Circuit 
Breaker
2 -  Main Breaker
3.  Move the fuel shutoff valve to the ON position (see 
Figure 31).
Figure 31 – Fuel Shutoff Valve in the ON Position
NOTICE
This generator is equipped with an automatic 
choke for starting. This system is always on and 
cannot be turned off. Do not attempt to make 
adjustments to the automatic choke or any other 
carburetor adjustments. Tampering with the 
automatic choke system may void your warranty. 
See an authorized Westinghouse service center for 
more information.
4.  Press the start button on the remote start key fob.
5.  The generator will turn over for 3 to 5 seconds and 
start.
6.  An engine warmup delay is programmed into the 
remote start cycle. After the generator is running, 
there will be a delay of electrical output for 15 
seconds.
7.  If the engine fails to start within 3 to 5 seconds, the 
engine will attempt to start five additional times. 
If the generator failed to start, the remote start 
indicator light will flash.
8.  If the generator fails to start after a total of six 
attempts, the start button on the key fob must be 
pushed again to begin another cycle of six start 
attempts.
STOPPING THE GENERATOR 
USING REMOTE START
1.  Make sure there is no load to any of the generator 
outlets.
2.  Press the stop button on the remote start key fob.
3.  The generator will run for an additional 15 seconds 
as it goes through a cooldown cycle before shutting 
off.