-  Write 2 to register 3005.  Valve will close and reset. 
 
6.  To restore the previous R and K values, write the value of R to register 7518 
and the value of K to 7520.  In case the old values are forgotten and the new 
values have not been saved to the valve, reset the valve by turning power off 
then on to restore R and K.  The following steps will also reset the valve; care 
must be taken, valve will close and reset. 
 
RESET valve routine: 
 
-  Write a password to register 3099. 
-  Write 1 to register 3005.  Wait 100 milliseconds. 
-  Write 2 to register 3005.  Valve will close and reset. 
 
10.4  Download Parameters 
 
All setup parameters, tables 15-20, can be written when you have the appropriate 
password.  New parameters can be downloaded to the XVG/eXVG as follows: 
 
-  Setup proper write-access level for the parameters. 
-  Write the new values to the registers. 
-  Perform Save Parameters routine. 
 
10.5  Re-Assign Device Address Procedure 
 
Register 
Number 
XVG/eXVG Parameter Name 
Description 
Type 
Write 
Access 
3005 IDM_SETUPCONNECT 
Setup 
Mode: 
1=Set Valve in Setup State, 2=Exit 
Setup and Reset CPU 
U16
 
W1 
3033 IDM_CALFLAGS 
Calibration 
Flags 
U16
 
W1 
3099 IDM_TESTSTR 
Test 
string, used for Modbus write access 
password. 
U16
 
W0 
3540 
IDM_SLAVEADDR 
Modbus slave address. Range: 1 to 247 
U16 
W2
 
 
Table 26:  Parameters Used to Assign Device Address 
 
XVG/eXVG default Modbus address is 1.  In case the Modbus address is forgotten, 
a new address can be assigned by using broadcast messages.  Perform the following 
steps; send all messages with device address 0: 
 
1.  Make a one-to-one connection between the Modbus master and the 
XVG/eXVG; no other Modbus device is present on the network.   
2.  Write a password to register 3099. 
3.  Write 1 to register 3005.  
4.  Write the new device address to register 3540. 
5.  Write 1 to register 3033.  Wait 100 milliseconds. 
 35