PACKAGE HEAT PUMP SPECIFICATIONS
26
PERFORMANCE TEST
All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section.  Indoor
air cubic feet per minute (CFM) as listed in the Performance Data Sheets:
If conditions vary from this, results will change as follows:
1.
As indoor dry bulb temperatures increase, a slight increase will occur in indoor air temperature drop (Delta T). Low
and high side pressures and power will not change.
2.
As indoor CFM decreases, a slight increase will occur in indoor temperature drop (Delta T). A slight decrease will
occur in low and high side pressures and power.
A properly operating unit should be within plus or minus 3 degrees of the typical (Delta T) value shown.
A properly operating unit should be within plus or minus 7 PSIG of the HI PR shown.
A properly operating unit should be within plus or minus 3 PSIG of the LO PR shown.
A properly operating unit should be within plus or minus 3 Amps of the typical value shown.
GPH13[42-60]H41**
EXPANDED PERFORMANCE DATA
 MODEL:  GPH1348H41**
HEATING OPERATION
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
0
-5
-10
MBh
55.9
53.0
49.8
46.6
44.5
43.1
40.1
36.9
32.4
29.9
27.5
26.0
25.0
22.5
19.9
17.4
14.8
12.1
DELTA  T
32.4
30.6
28.8
27.0
25.8
25.0
23.2
21.4
18.7
17.3
15.9
15.0
14.5
13.0
11.5
10.1
8.6
7.0
KW
3.72
3.65
3.58
3.52
3.48
3.45
3.38
3.32
3.40
3.33
3.26
3.22
3.19
3.12
3.05
2.98
2.90
2.83
AMPS
19.1
17.9
16.9
16.1
15.6
15.4
14.6
14.0
13.5
13.1
12.6
12.3
12.2
11.7
11.1
10.6
10.0
9.3
COP
4.40
4.24
4.07
3.88
3.74
3.66
3.46
3.26
2.79
2.63
2.47
2.37
2.30
2.11
1.91
1.71
1.49
1.25
EER
15.0
14.5
13.9
13.2
12.8
12.5
11.8
11.1
9.5
9.0
8.4
8.1
7.9
7.2
6.5
5.8
5.1
4.3
HI PR
366
351
337
323
315
309
297
285
273
261
250
244
240
231
222
213
205
198
LO PR
130
121
113
104
98
94
87
77
70
62
55
51
49
41
36
30
26
21
Above information is for nominal CFM and 70 degree indoor dry bulb.  Instantaneous capacity listed.
 MODEL:  GPH1360H41*
HEATING OPERATION
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
0
-5
-10
MBh
68.5
64.9
61.0
57.1
54.5
52.8
49.1
45.2
39.9
36.8
33.9
32.0
30.8
27.6
24.5
21.4
18.2
14.9
DELTA  T
34.3
32.5
30.6
28.6
27.3
26.4
24.5
22.6
20.0
18.4
17.0
16.0
15.4
13.8
12.3
10.7
9.1
7.5
KW
5.30
5.19
5.09
4.98
4.92
4.87
4.77
4.67
41.89
40.71
39.57
38.88
38.42
37.24
36.10
34.96
33.78
32.64
AMPS
22.8
21.3
20.1
19.0
18.4
18.0
17.1
16.3
15.7
15.1
14.5
14.2
14.0
13.4
12.6
12.0
11.2
10.3
COP
3.78
3.65
3.51
3.35
3.24
3.17
3.01
2.84
0.28
0.26
0.25
0.24
0.23
0.22
0.20
0.18
0.16
0.13
EER
12.9
12.5
12.0
11.5
11.1
10.8
10.3
9.7
1.0
0.9
0.9
0.8
0.8
0.7
0.7
0.6
0.5
0.5
HI PR
370
354
341
326
318
312
300
288
276
263
253
247
242
233
224
215
207
200
LO  PR
125
116
108
99
94
90
83
74
67
60
52
49
47
40
34
29
25
20
Above information is for nominal CFM and 70 degree indoor dry bulb.  Instantaneous capacity listed.