Watlow Electric Revision 5 Benutzerhandbuch

Seite von 71
60
10.4.1 Processor Reset
This Error Code is returned after :
ƒ
  Power-up reset
ƒ
  The watchdog timer resets the Master processor
ƒ
  The Master processor resets the Slave processor
10.4.2 Command Error
This Error Code is returned when the A32PID receives a command that is
not a Block Read or a Block Write.
10.4.3 Data Boundary Error
This Error Code is returned when:
ƒ
  A Read command attempts to read beyond the 32 byte boundary of
byte-size variables
ƒ
  A Read command attempts to read beyond the 64 byte boundary of
word-size variables
ƒ
  A Read command is received that specifies the number of bytes to read
as 0
ƒ
  AWritecommand attempts to write beyondthe32 byte boundary of
byte-size variables
ƒ
  A Write command attempts to write beyond the 64 byte boundary of
word-size variables
10.5. Data Table Addresses
Addresses
Variable
Number Size
Hex Byte Range Octal Word Range
Prop. Gain
32
Byte
0100 - 011F
200 - 217
Rate
32
Byte
0120 - 013F
220 - 237
Reset
32
Byte
0140 - 015F
240 - 257
Input Type
32
Byte
0160 - 017F
260 - 277
Output Value
32
Byte
0180 - 019F
300 - 317
Output Type
32
Byte
01A0 - 01BF
320 - 337
Output Filter
32
Byte
01C0 - 01DF
340 - 357
Cycle Time
32
Byte
01E0 - 01FF
360 - 377
Alarm Deviation
32
Byte
0200 - 021F
400 - 417
Setpoint
32
Word
0220 - 025F
420 - 457
Measured Value
32
Word
0260 - 029F
460 - 517
Ambients
08
Byte
02A0 - 02A7
520 - 523
Digital I/O's
01
Byte
02A8
524
Alarm Status
08
Byte
02B0 - 02B7
530 - 533
Heater Check
33
Byte
02BC
536
EEROM Save
---
-----
02BE
537
DACQ Input Type
64 Byte
02C0 - 02FF
540 - 577
DACQ Meas. Val.
64 Word
0300 - 037F
600 - 677