York UL R134A Benutzerhandbuch

Seite von 140
JOHNSON CONTROLS
52
High Efficiency Ratings
  – SI - 380V/60Hz
MODEL: YCIV0157E/V
 AIR TEMPERATURE ON - CONDENSER (°C)
LCWT
25.0
30.0
35.0
40.0
45.0
46.0
(°C)
KWi
KWi
COP
KWi
KWi
COP
KWi
KWi
COP
KWi
KWi
COP
KWi
KWi
COP
KWi
KWi
COP
5.0
525.0
123.1
3.9
515.6
139.0
3.4
503.3
156.2
3.0
487.8
176.4
2.6
449.0
192.6
2.2
441.1
196.0
2.1
6.0
539.7
124.0
3.9
530.4
140.2
3.5
518.1
157.4
3.0
500.9
177.3
2.6
460.8
193.4
2.2
452.7
196.7
2.2
7.0
554.7
125.0
4.0
545.4
141.3
3.5
533.0
158.5
3.1
514.0
178.2
2.7
472.8
194.1
2.3
464.5
197.5
2.2
8.0
569.9
126.1
4.1
560.7
142.4
3.6
548.1
159.7
3.2
527.2
179.1
2.7
484.9
195.0
2.3
476.5
198.2
2.3
9.0
585.2
127.1
4.2
576.2
143.5
3.7
563.5
161.0
3.2
540.5
180.0
2.8
497.0
195.9
2.4
488.4
199.1
2.3
10.0
600.7
128.2
4.2
591.8
144.7
3.7
579.1
162.2
3.3
554.0
180.9
2.9
509.5
196.8
2.4
500.6
200.0
2.4
11.0
616.4
129.2
4.3
607.7
145.8
3.8
594.9
163.5
3.4
567.6
181.9
2.9
522.3
197.7
2.5
513.2
200.9
2.4
12.0
632.2
130.3
4.4
623.8
147.0
3.9
610.9
164.8
3.4
581.2
182.9
3.0
535.2
198.6
2.5
525.9
201.8
2.4
13.0
648.3
131.3
4.5
640.1
148.3
4.0
627.2
166.2
3.5
595.0
183.8
3.0
548.3
199.5
2.6
538.8
202.7
2.5
MODEL: YCIV0177E/V
 AIR TEMPERATURE ON - CONDENSER (°C)
LCWT
25.0
30.0
35.0
40.0
45.0
46.0
(°C)
KWi
KWi
COP
KWi
KWi
COP
KWi
KWi
COP
KWi
KWi
COP
KWi
KWi
COP
KWi
KWi
COP
5.0
558.7
129.2
3.9
550.3
147.1
3.4
540.3
167.0
3.0
525.1
189.7
2.6
492.2
209.6
2.2
484.3
213.4
2.1
6.0
574.5
130.1
4.0
565.7
147.9
3.5
555.3
167.8
3.0
538.7
190.4
2.6
504.1
210.2
2.2
496.2
213.9
2.2
7.0
590.5
131.1
4.0
581.5
148.8
3.6
570.6
168.6
3.1
552.7
191.0
2.7
516.4
210.7
2.3
508.1
214.6
2.2
8.0
606.9
132.2
4.1
597.5
149.7
3.6
586.3
169.5
3.2
566.8
191.7
2.7
528.8
211.3
2.3
520.3
215.1
2.3
9.0
623.5
133.4
4.2
613.9
150.7
3.7
602.3
170.4
3.3
581.3
192.4
2.8
541.5
211.8
2.4
532.8
215.7
2.3
10.0
640.4
134.6
4.3
630.5
151.8
3.8
618.5
171.4
3.3
596.0
193.1
2.9
554.4
212.3
2.4
545.5
216.2
2.4
11.0
657.7
136.0
4.4
647.5
153.0
3.9
635.1
172.5
3.4
610.9
193.9
2.9
567.6
212.9
2.5
551.5
211.4
2.4
12.0
675.2
137.4
4.4
664.8
154.3
3.9
652.0
173.6
3.5
626.1
194.7
3.0
580.9
213.4
2.5
557.2
206.6
2.5
13.0
693.1
139.0
4.5
682.3
155.6
4.0
669.2
174.8
3.5
641.6
195.5
3.1
594.4
214.0
2.6
562.8
202.0
2.6
MODEL: YCIV0187E/V
 AIR TEMPERATURE ON - CONDENSER (°C)
LCWT
25.0
30.0
35.0
40.0
45.0
46.0
(°C)
KWi
KWi
COP
KWi
KWi
COP
KWi
KWi
COP
KWi
KWi
COP
KWi
KWi
COP
KWi
KWi
COP
5.0
621.1
143.4
3.9
611.6
164.1
3.4
600.1
187.0
3.0
582.8
211.7
2.6
547.1
228.0
2.2
538.6
230.9
2.2
6.0
638.5
144.3
4.0
628.9
164.8
3.5
617.0
187.7
3.0
598.1
212.0
2.6
560.8
228.4
2.3
552.0
231.3
2.2
7.0
656.2
145.3
4.1
646.4
165.6
3.5
634.2
188.4
3.1
613.8
212.3
2.7
574.6
228.7
2.3
565.6
231.6
2.3
8.0
674.1
146.4
4.1
664.2
166.5
3.6
651.7
189.3
3.2
629.7
212.6
2.7
588.8
229.0
2.4
579.5
232.0
2.3
9.0
692.3
147.7
4.2
682.2
167.5
3.7
669.4
190.2
3.2
645.8
212.9
2.8
603.2
229.2
2.5
593.7
232.2
2.4
10.0
710.7
149.0
4.3
700.4
168.6
3.8
687.3
191.1
3.3
662.3
213.3
2.9
617.8
229.4
2.5
608.1
232.4
2.4
11.0
729.4
150.5
4.4
719.0
169.8
3.9
705.6
192.2
3.4
678.9
213.6
3.0
632.7
229.6
2.6
622.8
232.6
2.5
12.0
748.4
152.0
4.4
737.8
171.1
3.9
724.1
193.3
3.5
695.7
214.0
3.0
647.8
229.7
2.6
632.7
229.6
2.6
13.0
767.7
153.7
4.5
756.9
172.4
4.0
742.9
194.5
3.5
712.8
214.4
3.1
663.1
229.9
2.7
638.4
224.0
2.7
NOTES:
1.  kWo 
=  Unit kW Cooling Capacity Output
2.  kWi  
=  Compressor kW Input
3.  COP 
=  Coefficient of Performance (includes condenser fan power)
4.  LCWT  =  Leaving Chilled Water Temperature
5.  Ratings based on 0.168 l/s cooler water per ton, and 0.018 (m
2
 – °C)/kW