York Patio Furniture P2DHX16F12001 Benutzerhandbuch

Seite von 36
 
 
21 
 
 
 
IDLE STATE 
THERMOSTAT CALLS FOR HEAT 
SAFETY CHECK FOR FLAME 
(5 SEC.)
 
BURNER MOTOR & IGNITOR START 
SOLENOID VALVE OPENS 
TRIAL FOR IGNITION 
15 SEC.
BURNER FLAME MONITORED 
CARRYOVER STATE 
• 
Provides continuous spark 
• 
LED diagnostic light ON 
• 
Start Carryover Timer 
CARRYOVER TIMER EXPIRES 
RUN STATE 
• 
Ignitor turns off. 
THERMOSTAT SATISFIED 
R7184 SHUTS OFF: 
• 
Burner Motor 
• 
Solenoid Valve 
• 
LED Diagnostic Light 
RETURNS TO IDLE STATE 
FLAME
FLAME
FLAME
FLAME
NO FLAME
NO FLAME
FLAME LOST
FLAME LOST
REMAINS IN IDLE STATE
R7184 
SEQUENCE of 
OPERATION 
LOCKOUT STATE 
R7184: 
• 
Shuts off burner motor 
• 
Shuts off igniter 
• 
Shuts off Solenoid Valve 
• 
Fast Flashes LED Diagnostic 
Light
TO EXIT LOCKOUT 
PRESS RESET 
RECYCLE TIMER STARTS 
R7184: 
• 
Shuts off Solenoid Valve 
• 
Shuts off Ignitor 
• 
Shuts off Burner Motor 
• 
Slow Flashes LED diag-
nostic light
RECYCLE TIMER EXPIRES 
(60 SECONDS 
FLAME LOST