CORNER CLEARANCES
36"
lOCATINg STOvE
Proper clearances must be maintained for adequate 
air  circulation. Adequate  ventilation  must  be  
provided while operating this stove.
1.  The  stove  must  be  placed  on  solid  con-
crete,  solid  masonry,  or  on  an  listed 
floor  protector,  such  as  Hy-C  or  Impe-
rial Model UL 5463BK when installed on a  
combustible  floor.  The  base  must  extend  at 
least 18” beyond the front, rear and sides of the 
stove, and must extend under the stove pipe if 
it is elbowed towards a wall (see figure 5 and 
consult local building codes and fire protection 
ordinances.)
2.  The stove must have its own flue. 
DO NOT 
CONNECT THIS  UNIT TO  A  CHImNEY 
FLUE SERVING OTHER APPLIANCES.
3.  After observing the clearances to combustible 
materials  (figure  2  –  4),  locate  your  floor  
protector  accordingly  (figure  2)  and  care-
fully place the stove in your selected location.   
Install stove pipe, stove pipe damper, elbows, 
and  thimble  as  required,  utilizing  either  a  
recently  cleaned  and  inspected  6”  masonry 
chimney or a 6” i.d. listed chimney. Maximum 
64 square inches.
FLOOR
PROTECTOR
DASHED LINE SHOWS
HORIZONTAL CHIMNEY
CONNECTOR AND
ADDITIONAL FLOOR
PROTECTION REQUIRED
BACKWALL
54"
(TOP VIEW)
36"
18"
18"
18"
36"
63"
18"
SIDEWALL
COMBUSTIBLE
CONSTRUCTION 
ACCORDING TO
NFPA 211
COMBUSTIBLE
CONSTRUCTION 
ACCORDING TO
NFPA 211
4.  Use 6” round black stove pipe. DO NOT use 
galvanized duct pipe. Secure pipe sections with 
three (3) sheet metal screws in each stove pipe 
and/or elbow joint to firmly hold the pipe sec-
tions  together. 
DO  NOT  CONNECT THIS 
STOVE TO ANY AIR DISTRIBUTION OR 
DUCT SYSTEm.
5.  Recheck  clearances  from  the  stove,  
connector  stove  pipe,  and  corner  clearances 
using  the  illustrations  (figure  2,  3  &  4)  and  
your  local  building  codes  or  fire  protection  
ordinances.  
 
NOTE: Drywall faced with brick or stone must 
be considered a combustible surface.
6. 
D O   N OT   I N S TA L L   T H I S   S TOV E 
IN A mOBILE HOmE, TENT OR TRAILER. 
(NO EXCEPTIONS)
7.  The  clearances  provided  are  minimum  
dimensions.  Installation  of  this  stove  must  
comply  with  your  local  building  code  rul-
ings.
8.  This stove is NOT a UL listed stove.
Continued on next page
Fig. 2      Minimum Clearance Dimensions from Combustible Surfaces      Fig. 3
MiniMuM ClearanCes
To CoMbusTible surfaCes
unit to sidewall ....................................36 inches
unit to backwall ...................................36 inches
unit Corner to Wall ................................36 inches
Pipe Connector to backwall ......................38 inches
Pipe Connector to Ceiling ........................18 inches
Fig. 4 – Top View
 Minimum Corner Clearances from  
Combustible Surfaces