Vogelzang International SR57E Benutzerhandbuch

Seite von 12
Page 4 
/ SR57E
 
VGZ-004 / 20110524.0
pIpE INSTAllATION
4.  Use  6”  round  black  stove  pipe,  not  galvanized 
stove  pipe.  Secure  pipe  sections  with  three 
(3)  sheet  metal  screws  in  each  stove  pipe  and/
or  elbow  joint  to  firmly  hold  the  pipe  sections  
together. 
DO  NOT  CONNECT THIS  STOVE 
TO  ANY  AIR  DISTRIBUTION  OR  DUCT 
SYSTEm.
5.  R e c h e c k   c l e a r a n c e s   f r o m   t h e   s t o v e ,  
connector  stove  pipe,  and  corner  clearanc-
es  using  the  illustrations  (figure  1  &  2)  and  
lOCATINg STOvE continued…
1.  The smooth end of the stovepipe fits over the cast 
iron collar. To attach, simply hand form the smooth 
end of the round stove pipe into an oval shape (fig. 
4). Drill & secure with a minimum of three (3) sheet 
metal screws.
2.  Horizontal  pipe  runs  must  slope  upwards  
towards the chimney at least 1/4” per foot of hori-
zontal run.
3.  You must have at least 18 inches of clearance be-
tween any horizontal piping and the ceiling.
4.  The pipe cannot extend into the chimney flue (figure 
5).
5.  Secure  pipe/elbow  sections  with  three  (3)  sheet 
metal  screws  at  each  joint  to  make  the  piping 
rigid.
Fig. 5 – Stovepipe/Flue Connections
CORRECT               wRONG              wRONG
CAUTION:  kEEP  FURNISHINGS  AND  OTHER   
COmBUSTIBLE mATERIALS AwAY FROm THE 
STOVE.
36"
36"
CORNER CLEARANCES
mINImUm CLEARANCES
TO COmBUSTIBLE SURFACES
6.  It  is  recommended  that  no  more  than  two  (2) 
90°  bends  be  used  in  the  stovepipe  installa-
tion. The  use  of  more  than  two  90°  bends  may  
decrease  the  amount  of  draw  and  possibly 
cause  smoke  spillage. Where  possible,  use  only  
corrugated  (nonadjustable)  elbows.  These  
provide a better seal.
7.  The chimney connector must not pass through an 
attic or roof space, closet, or any concealed space, or 
floor, ceiling, wall or combustible construction.
your  local  building  codes  or  fire  protection  
ordinances.  
 
NOTE: Drywall faced with brick or stone should 
be considered a combustible surface.
6. 
D O   N O T   I N S TA L L   T H I S   S T O V E 
IN  A  mOBILE  HOmE  OR  TRAILER. 
(NO EXCEpTIONS)
7.  The  clearances  provided  are  minimum  
dimensions.  Installation  of  this  stove  must  
comply with your local building code rulings.
8.  This stove is NOT a UL listed stove.
Fig. 4 – Hand-form pipe to fit stove collar
NOTE:  STOVE  PIPE  IS  NOT  INClUDED.   
TO  PURCHASE  PIPE, VISIT YOUR  LOCAL 
HARDwARE,  HOmE  OR  BUILDING  CEN-
TER.  SEE “LOCATING  STOVE”  PAGE  3  FOR   
ADDITIONAL SPECIFICATIONS.
Unit to Sidewall ....................... 36 inches
Unit to Backwall ...................... 36 inches
Unit Corner to wall .................. 36 inches
Pipe Connector to Ceiling ...... 18 inches
Fig. 3 – Top View
 Minimum Corner Clearances from  
Combustible Surfaces