Utica Boilers H2OBT Installationsanweisungen

Seite von 8
5
Buffer Tank Sizing - Calculating Capacity
The buffer tanks are a simple, cost effective way to improve overall system efficiency by reducing unnecessary equipment 
short cycling. The recommended capacity or volume of a buffer tank is based on four variables.
1.  The duration of the heating or cooling source “on time”. (minutes)
 
The desired length of “on time” for each run cycle depends on the type of equipment used. Heat pump and 
chiller manufacturers typically recommend a minimum of 5 to 10 minutes on time, and boiler manufacturers may 
recommend a minimum of 10 minutes “on time”. Check with your equipment manufacturer. Generally, the longer the 
“on time”, the higher the overall operating efficiency.
2.  The minimum rate of heat input. (BTU/HR)
 
This is based on the heat pump or chiller output, or the boiler output at the minimum firing rate if the boiler has a 
variable input system that ramps input down as the demand decreases.
3.  The minimum system load (BTU/HR)
 
This is the demand placed on the system with the smallest zone calling for heat.
4.  The allowable tank temperature rise. (deg. F)
 
This varies depending on the type of heating or cooling system used, and on the design of the distribution system. Chillers 
may require a tight, (6 deg. F), differential to assure good dehumidification and prevent freezing, heat pumps may require 
a 10 deg. F differential to maintain a high COP, and boilers with hydronic heating distribution systems may require a 
differential anywhere between 10 to 40 deg. F depending on the application.
The following formula determines the tank volume:
V = T X (Q heat input - Q min. heat load)
               Tank temp. rise X 500
V = Buffer tank volume (gallons)
T = desired heat source “on cycle” (min.)
Q heat source = heat source output (BTU/HR)
Q min. heat load = heat output to minimum load
Tank temp rise (deg.F)
Water to Water Heat Pump Example: Town and Country Mechanical wants a minimum heat pump on time of 10 minutes. The 
heat pump output is 46,500 BTU/HR. The smallest zone is 7,000 BTU/HR bathroom. The allowable temperature differential 
is 90 to 100 deg. F for the radiant heat zones.
V = 10X (46,500 - 7,000) = 79.0 Gallons minimum volume. Choose the HF-80BT buffer tank.
          (100-90) x 500