14.4 Annual Shut Down Procedure
1. 
Turn off gas to boiler as described in “To Turn Off Gas 
To Appliance” Section 13.3 page 24.
2. 
If heating system is to remain out of service during 
freezing weather and does not contain antifreeze, drain 
system completely. If boiler will be exposed to freezing 
temperatures, drain condensate lines.
14.5 Annual Examination And Cleaning Of Boiler 
Components
1. 
Following service procedures must be performed by 
qualified service agency. Boiler owner should not 
attempt these steps.
2. 
Before servicing, turn off electrical power to boiler at 
service switch. Close manual gas valve to turn off gas 
supply to boiler.
3. 
Examine flue passages by removing blower/burner 
assembly from casting. Procedure for examining and 
cleaning the burner is described below.
4. 
Clean any buildup of sediment or aluminum oxide (white 
powdery or flaky substance) in flue passages as follows:
A.  Remove jacket front and top panels.
B.  Confirm manual gas valve is closed and disconnect 
gas line to gas valve at union. Disconnect pressure 
switch hoses to gas valve and air inlet.
C.  Disconnect wires to gas valve and igniter.
D.  Loosen but do not remove five nuts attaching 
blower adapter assembly to boiler.
E.  Remove two igniter screws and carefully remove 
igniter.
F.  Remove five nuts and remove blower adapter 
assembly, burner, and gaskets.
14 - MAINTENANCE AND CLEANING
G.  Aluminum oxide deposits are water soluble and 
may be rinsed away by inserting hose into burner 
opening of casting and slowly run water through 
flue side of boiler and out condensate drain. Debris 
rinsed away by this method will exit through 
condensate drain. Be wary of drain lines getting 
clogged and causing water to back up in the bottom 
of casting.
H.  Use flexible handle nylon brush to loosen sediment 
and aluminum oxide on all accessible heating 
surfaces of boiler. Take care not to get brush stuck 
in heat exchanger.
I.  After brushing and rinsing, remove any remaining 
loosened sediment using shop vacuum with snorkel 
attachment.
J.  Inspect burner for any foreign matter in flame 
ports or inside burner. Remove any foreign matter 
by blowing with compressed air or vacuuming. If 
burner cannot be cleaned, it must be replaced.
K.  Reinstall burner and gaskets and position blower 
adapter assembly over studs. Install five nuts do 
not tighten. Reinstall igniter and igniter gasket 
and fasten with two screws. Tighten five nuts 
holding blower adapter assembly.
L.  Connect gas line to gas valve, pressure switch hose 
to gas valve and air inlet assembly, igniter wires, 
and gas valve wires.
5. 
Inspect condensate trap. Clean out any foreign material 
visible in condensate lines.
A.  Inspect for sediment or blockage.
B.  Flush out with water or vacuum.
C.  Follow instructions in, “Filling Condensate Trap With 
Water.”
6. 
Inspect flue connector.
A.  Loosen clamp on vent tee side of 2” flexible 
coupling that connects vent tee to exhaust port.
B.  Inspect interior of vent tee. Clean any buildup of 
sediment on inside surface.
C.  Reconnect 2” flexible coupling to vent tee. 
NOTICE
Verify proper operation after servicing.
NOTICE
Perform regular service and maintenance by qualified 
service agency at least once every 12 months to 
assure safe, trouble free operation and maximum 
efficiency.
 WARNING
Following service procedures must be performed by 
qualified service agent. Boiler owner shall not attempt 
these steps. Failure to do so could result in death or 
serious injury.
!
  