GP Series Portable Chillers 
Chapter 2: Functional Description 
10 of 64 
High Pressure Cutout 
This electro-mechanical cutout device opens the compressor control circuit if the refrigeration 
system compressor discharge pressure exceeds 575 psi..  
Note: 
The high-pressure cutout is a manual reset device typically mounted on the 
compressor discharge line inside the mechanical cabinet. Call a refrigeration 
service technician to analyze the problem and reset the control.  
Low Pressure Cutout (no switch but done through the transducer) 
There are two pressure transducers in the refrigeration piping – one on the suction line before 
the compressor and one on the discharge line after the compressor.  Within the program there 
are four settings that warn and fault based on these two pressure transducers.  The low suction 
warning is set for 110 psig (758 kPa), and the compressor will fault at 100 psig (689 kPa).  
The low discharge warning is set for 200 psig (1,379 kPa), and the compressor will fault at 
180 psig (1,241 kPa).  To prevent nuisance tripping there are delays built in to the program. 
Note: 
Call a refrigeration service technician to analyze the problem to prevent 
recurring low pressure faults. 
Flow Switch  
The thermal dispersion flow switch cutout device, mounted in the process piping, shuts down 
the chiller if it senses that the water/glycol flow rate through the evaporator has dropped 
below an acceptable level. The flow switch opens the control circuit and shuts down the 
pumps and the chiller. 
Remote Start/Stop Interlock 
An additional contact is provided to allow the remote starting or stopping of the chiller. To 
use this feature, remove the jumper between terminals 1 and 23, and supply a switch or dry 
contact interlock connected in series between these two terminals. Refer to the schematic 
inside the control enclosure door.
 
 
2-5 Optional 
Features 
Options marked with “*” indicate options that can be factory installed or retrofitted in the 
field.  
Automatic Water Make-Up*. Not available on chillers less reservoir tank. Includes an 
electric water solenoid valve, a level sensing pressure switch mounted in the reservoir tank, 
and the necessary internal piping to connect the chiller to a make-up water source.  See 
Appendix for typical piping diagrams. 
Caution!  Customer piping must provide backflow protection and venting of tank to 
atmosphere to prevent over-pressurization of the reservoir tank (not needed for 
open tank). See 
Error! Reference source not found. on page Error! Bookmark 
not defined.
Process Water Side-stream Filter*. Not available on chillers less pump and reservoir tank. 
This option includes a 50 micron filter, flow meter, ball valve for throttling water flow, and 
the necessary piping to provide constant filtering of the process water at about one gallon per 
minute (1 gpm/3.8lpm).