Chapter 7: Appendix 
50 of 64 
7-6  Typical Ductwork for Air-Cooled Chillers 
 
Fan 
60 Hz Discharge 
air volume 
50 Hz Discharge 
air volume 
Model 
HP kW  CFM m
3
/min CFM m
3
/min 
GPAC-20 0.5 
0.4  4230
120 3525 100 
GPAC-30 1.0 
0.7  6343
180 5286 150 
GPAC-40 1.0 
0.7  8458
240 7048 200 
GPAC-50  2.0 1.5  12687
360 10573 300 
 
When locating your air-cooled portable chiller and designing its ductwork, note any potential high 
temperature conditions when discharging into your building and any negative pressures with the building 
when discharging air outside. 
Notes: 
• Customer use of ductwork requires the high pressure fan option. • Allow 30” (77 cm) minimum 
clearance around the chiller footprint to facilitate free passage of cooling air and service accessibility 
• 
Size the ductwork for maximum capacity 
• Support ductwork from the building structure, not off of the 
chiller 
• Back draft damper to outside must be closed at all times when fan/blower is not operating •