5.  SYSTEM PARAMETERS
Parameter
Function
Range
[Default]
Description / Notes
G85139-H1750-U049-B
© Siemens plc 1997
26/09/97
24
P022  
Maximum analogue frequency
(Hz)
0 - 400.00
[50.00]
Frequency corresponding to the highest analogue input value, i.e.
10 V, determined by P023. This can be set to a lower value than P021
to give an inverse relationship between analogue input and frequency
output.
i.e.
Note:
The output frequency is limited by values entered for
P012/P013.
P023  
Analogue input function
0 - 2
[0]
0 = 0 V to 10 V
1 = 2 V to 10 V
2 = 2 V* to 10 V
* The inverter will come to a controlled stop if V < 1 V.
WARNING: The motor can automatically run without a
potentiometer or voltage source connected between
pins 3 and 4.
WARNING: With P023=2, the inverter will automatically start
when V goes above 1 V. This equally applies to
analogue and digital control (i.e. P006 = 0 or 1).
P024  
Analogue setpoint addition
0 - 2
[0]
If the inverter is not in analogue mode (P006 = 0 or 2), setting this
parameter to ‘1’ causes the analogue input value to be added.
0 = No addition.
1 = Addition of the analogue setpoint (defined by P023) to the
fixed frequency or the motor potentiometer frequency.
2 = Scaling of digital/fixed setpoint by analogue input (P023) in
the range 0 - 100%.
Note:
By selecting a combination of reversed negative fixed
frequency settings and analogue setpoint addition, it is
possible to configure the inverter for ‘centre zero’ operation
with a +/-5 V supply or a 0 - 10 V potentiometer so that the
output frequency can be 0 Hz at any position, including the
centre position.
P027  
Skip frequency 2 (Hz)
0 - 400.00
[0.00]
See P014.
P028  
Skip frequency 3 (Hz)
0 - 400.00
[0.00]
See P014.
P029  
Skip frequency 4 (Hz)
0 - 400.00
[0.00]
See P014.
P031  
Jog frequency right (Hz)
0 - 400.00
[5.00]
Jogging is used to advance the motor by small amounts. It is controlled
via the JOG button or with a non-latching switch on one of the digital
inputs (P051 to P053).
If jog right is enabled (DINn = 7), this parameter controls the frequency
at which the inverter will run when the switch is closed. Unlike other
setpoints, it can be set lower than the minimum frequency.
P032  
Jog frequency left (Hz)
0 - 400.00
[5.00]
If jog left is enabled (DINn = 8), this parameter controls the frequency
at which the inverter will run when the switch is closed. Unlike other
setpoints, it can be set lower than the minimum frequency.
f
V
P021
P021
P022
P022