2/16                              CC1B-Hints-en 
Preliminary
                                 04.02.2003                                        HVAC Products 
2. Hints 
 
2.1 Getting started with the RWF40 menu
  
 
The RWF40 menu system has three Levels, beyond the Basic Display,  
 the 
User Level,  
 the 
Parameter Level and  
 the 
Configuration Level.
 
 
 RWF40 user manual Section 6 Operation.
 
 
 
2.1.1 Start with the Basic Display 
 
Shown at the right is the basic display. 
 
The upper, larger, 4 digit 
red
 LEDs,  (
180
will be referred to as, the ‘Actual value display’.  
 
The lower, smaller, 4 digit 
green
 LEDs, (
180
will be referred to as, the ‘Setpoint display’. 
 
 
The current configuration of your specific controller  
will determine which levels you will be allowed to access.
 
 
C112 must be xxx0 to access the configuration level.
 
 
The C112 locking code can only be adjusted by the manufacturer. 
 
 
All controllers will return to the basic display  
automatically, if no key is pressed for 30 seconds.
 
 
The RWF40 configuration codes  
(C111, C112, and C113) are all four digits.  
 
The x’s used in the explanations in this manual  
represent a ‘don’t care’ digit in the code,  
so, xxx0 could mean 1000, 2100, 5430, etc,  
and we are only concerned with the ‘non-x’ digits. 
 
 
C112 code summary :
 
 
C112 code 
xxx0 
Locks nothing 
C112 code 
xxx1  
Locks the Configuration Level 
C112 code  
xxx2   
Locks the Parameter Level 
C112 code 
xxx3  
Locks all levels and keys
 
 
 
2.1.2 User Level
 
 
From the basic display,  
you may advance to the user level, 
by pressing   and releasing it. 
 
The actual value display, (
180
)
 
shows the setpoint you are adjusting or viewing. 
 
The setpoint display, (
SP 1
shows the parameter you are adjusting or viewing. 
 
You can adjust the values, within limits, for 
SP1, SP2, dSP, view tA, SP.E, 
depending on your specific configuration. 
 
To adjust user level values, please see the 
4 How to change a setpoint “,  
 
or 
 RWF40 user manual Section 6.2.1. 
 
2.1.3 Parameter Level
 
 
From the user level you may advance to the parameter level,  
by pressing  
 and holding, for 3 seconds,  
and then releasing it.  
 
 C112 must be xxx0 or xxx1, to access this level. 
 
The actual value display, (
0
shows the parameter ’s actual value.  
 
The setpoint display, (
AL
shows the parameter you are adjusting or viewing. 
 
You can adjust the values for AL, Hyst, Pb.1,  
dt, rt,  HYS.1, HYS.2, HYS.3, q, H, and P, 
depending on your specific configuration.
 
 
 
To adjust parameter values, please see  
3 How to adjust parameters “,  
 
or  
RWF40 user manual Section 7.
 
 
 
2.1.4 Configuration Level 
 
From the parameter level you may advance to the configuration level, 
by pressing 
 and holding, again for 3 seconds,  
and then releasing it.  
 
 C112 must be xxx0 to access this level. 
 
The actual value display, (
9030
shows the configuration item’s actual value.
  
 
The setpoint display, (
C111
shows the configuration item you are adjusting. 
 
You can adjust the values, within limits, for  
C111, C112, C113, SCL, SCH, SCL2, SCH2,  
SPL, SPH, OFF1, OFF2, OFF3, and dF1 
depending on your specific configuration. 
 
 
To adjust configuration values, please see the  
“2 How to configure our RWF40 “,  
 
or  
 RWF40 user manual Section 8.
 
 
 
Return to the Basic Display  
 
You may exit any level, and return to the basic display  
at any time, in two ways. 
 
First, to exit immediately, press  
  and release it. 
 
The second way is to simply wait 30 seconds, and the  
controller will automatically return to the basic display.