 OPERATION 
6
43
SITRANS FX300
www.siemens.com/flow
06/2009 - SFIDK.PS.050.F2.02   A5E02100423
Totalizer / pulse output
The base units for the totalizer and the pulse output are m
m
m
m
3
33
3
 for volume,
m
m
m
m
3
33
3
 norm. for standard volume and kg
kg
kg
kg for mass.
The unit and the conversion factor can be changed in menu item 3.2.8 "Tot.Conf.". User defined 
units (User Def.) can be selected and entered. The conversion factor of the unit must always be 
entered based on the base unit.
The maximum pulse output frequency is 0.5 Hz. To ensure that the pulse output does not exceed 
0.5 Hz, the conversion factor of the totalizer must be selected and set accordingly. The pulse 
output represents an exact copy of the whole number value of the internal totalizer.
Max. pulses per hour
Example
Menu items
6.2.6  Measures in the event of faulty indications
If the indications on the display or the responses to keypad commands are faulty, you have to do 
a hardware reset. Switch the power supply OFF and ON again.
fmax. ≤ 0.5 Hz
1 pulse-break ≥ 2 seconds
Max. pulses / hour = 1800
1800
1800
1800 pulses
Flow Qmax.
Factor A1 Coef.
Pulses / litre
Pulses / h
Comment
5.6 m
3
/h
0.001
1 pulse / 1 litre
5600
not possible
0.01
1 pulse / 10 litres
560
560 < 1800 = ok.
1.1.3
Maes.Inst
Volume / Standard volume / Mass
1.1.4
Max. Flow
Unit (User Def.) / Text / A1 Coeff. / Max. Flow
Max. Flow
Max. Flow
Max. Flow / Flow Displ
3.2.5
Function P
Yes
Yes
Yes
Yes / No
3.2.7
Totalizer
Tot. on
Tot. on
Tot. on
Tot. on / Tot. off
3.2.8
Tot. Conf.
User def. / Unit Text / A1 Coeff.
User def. / Unit Text / A1 Coeff.
User def. / Unit Text / A1 Coeff.
User def. / Unit Text / A1 Coeff.  / Preset Value / Reset / Display
MA_Siemens_Sitrans_FX300_R02_en_PRT.book  Page 43  Monday, June 22, 2009  8:17 AM