Point Database 
Siemens Building Technologies, Inc. 
 
21 
Description Address  Application 
Description 
DAY.NGT 
{29} 
2583, 2584, 2590 
Indicates the mode in which the controller is operating.  
Day temperature setpoints are used in day mode.  
Night temperature setpoints are used in night mode. This 
point is normally set by the field panel. 
CLG CMP1 ON 
30 
2584 
Value, in percent, that the cooling temperature control loop 
output must exceed for cooling compressor 1 to turn ON. 
Actual turn on is subject to the CLG1 MlN OFF time being 
expired. 
CLG CMP1 OFF 
31 
2584 
Value, in percent, that the cooling temperature control loop 
output must go below for cooling compressor 1 to turn OFF. 
Actual turn off is subject to the CLG1 MlN ON time being 
expired. 
CLG1 MlN OFF 
32 
2584 
Minimum time, in minutes, that cooling compressor 1 will 
remain OFF before turning ON. 
CLG1 MlN ON 
33 
2584 
Minimum time, in minutes, that cooling compressor 1 will 
remain ON before turning OFF. 
CLG CMP2 ON 
34 
2584 
Value, in percent, that the cooling temperature control loop 
output must exceed for cooling compressor 2 to turn ON. 
Actual turn on is subject to the CLG 2 MIN OFF time being 
expired. 
CMP3 ON 
34 
2583 
Value, in percent, that the active temperature control loop 
output must exceed for compressor 3 to turn ON. Actual 
turn on is subject to the CMP3 MlN OFF time being expired. 
CLG CMP2 OFF 
35 
2584 
Value, in percent, that the cooling temperature control loop 
output must exceed for cooling compressor 2 to turn OFF. 
Actual turn off is subject to the CLG2 MIN ON time being 
expired. 
CMP3 OFF 
35 
2583 
Value, in percent, that the active temperature control loop 
output must go below for compressor 3 to turn OFF. Actual 
turn off is subject to the CMP3 MlN ON time being expired. 
CLG2 MIN OFF 
36 
2584 
Minimum time, in minutes, that cooling compressor 2 will 
remain OFF before turning ON. 
CMP3 MlN OFF 
36 
2583 
Minimum time, in minutes, that compressor 3 will remain 
OFF before turning ON. 
CLG2 MlN ON 
37 
2584 
Minimum time, in minutes, that cooling compressor 2 will 
remain ON before turning OFF. 
CMP3 MlN ON 
37 
2583 
Minimum time, in minutes, that compressor 3 will remain ON 
before turning OFF. 
DAMPER TYPE 
38 
2583, 2584 
FLOAT indicates that a floating control damper is used. 
SPRING indicates that a spring return damper is used. 
Valid input: FLOAT or SPRING
AO DIR.REV 
39 
2583, 2584 
Configuration setup code for AO. Allows the AO to be direct 
(normally closed) or reverse acting (normally open). 
AOV1 
{40} 
2583, 2584, 2590 
Analog output 1 controls a 0 to 10V signal.