Siemens BACnet Heat Pump Controller - Multi-Stage Owner’s Manual 
26  
Siemens Building Technologies, Inc. 
Description Address  Application 
Description 
SWITCH DBAND 
90 
2583, 2584 
Temperature range in degrees that is compared to the 
difference between CTL TEMP and CTL STPT. The 
difference must exceed this value for temperature control 
mode to change over. Changeover is also subject to the 
active temperature control loop output being below SWITCH 
LIMIT and SWITCH TIME being expired. 
NGT MA CTL 
{91} 
2583, 2584 
YES indicates that mixed air control should occur during 
night mode. NO indicates that mixed air control will not 
occur during night mode. 
Valid input: YES or NO
CTL STPT 
{92} 
2583, 2584 
Actual setpoint value being used as input for the active 
temperature control loop. 
MA STPT 
{93} 
2583, 2584 
Setpoint of the mixed air control loop. 
EHEAT 2 ON 
94 
2583 
Value, in percent, that the heating loopout must exceed for 
the second stage of electric heat to turn ON. 
EHEAT 3 ON 
95 
2583 
Value, in percent, that the heating loopout must exceed for 
the third stage of electric heat to turn ON. 
CAL TIMER 
96 
2583, 2584, 2590 
Time interval, in hours, between the calibration sequence. 
AOV 3 
{97} 
2583, 2584, 2590 
Analog output 3 controls a 0 to 10V signal. 
LOOP TIME 
98 
2583, 2584 
Time, in seconds, between control loop calculations. 
ERROR STATUS 
{99} 
2583, 2584, 2590 
Status code indicating any errors detected during controller 
power up. A status of 0 indicates there are no problems. 
CLG D GAIN 
102 
2583, 2584 
Derivative gain value for the cooling temperature control 
loop. 
CLG BIAS 
103 
2583, 2584 
Biasing of the cooling temperature control loop.  
See CLG LOOPOUT. 
HTG D GAIN 
104 
2583, 2584 
Derivative gain value for the heating temperature control 
loop. 
HTG BIAS 
105 
2583, 2584 
Biasing of the heating temperature control loop.  
See HTG LOOPOUT. 
1. 
Points not listed are not used in this application. 
2. 
Point numbers that appear in brackets { } may be unbundled at the field panel.