SITRANS LU01 – INSTRUCTION MANUAL
Page 103
mmm
mm
Tr
oubl
esho
ot
ing
Increase the Confidence Threshold (small amounts at a time) while observing the results. 
If performance is not improved return the Confidence Threshold to the preset value. 
Connect an oscilloscope to the SITRANS LU01, (see Enhancement Parameters Scope 
Displays, P810). While monitoring the Echo Marker, select the Algorithm (P820) best 
suited to the material/conditions. 
If the Area algorithm is used and narrow noise spikes are evident on the (long shot) Echo 
Profile, turn the Spike Filter (P821) on and/or widen the Narrow Echo Filter (P822). Also, if 
the true echo has jagged peaks, use Reform Echo (P823). 
If multiple echoes appear on the Echo Profile, typical of a flat material profile (especially if 
the vessel top is domed), use the first Algorithm. 
If the Echo Profile repeatedly switches from short to long, adjust the Short Shot Range 
(P852) to stabilize the shot mode used for the echo evaluation. Also, adjust the Short Shot 
Bias to increase (or decrease) the amount of preference given to short shot echoes over 
long shot echoes. 
Should a stable measurement still not be attainable, contact Siemens Milltronics or your 
local distributor.