Preparing for Installation  
 
Keypad Options 
All Essex Keypads are designed to perform reliably in even the 
most extreme environmental conditions.  Operating 
temperatures can range from -40
°C to +70°C (-40°F to 160°F). 
The KE-265 is compatible with any of the following Keypad 
styles/configurations
:
 
System Components  
There are four primary components to be installed: 
 
 
 
 
 
 
Part Number *  Description 
KP-5S 
KP-5SL 
KP-5DI 
KP-5SI 
KP-34S 
KP-34B 
KP-34K 
KP-26TS 
KP-26TB 
KP-26TI 
KP-26TR 
5-Pad Stainless Steel 
5-Pad Stainless Steel w/ LED 
5-Pad Duranodic Illuminated 
5-Pad Stainless Illuminated 
12-Pad 3x4 w/ Stainless Steel Bezel 
12-Pad 3x4 w/ Brass-Finished Bezel 
12-Pad 3x4 w/ Black Bezel 
Thinline 2x6 w/ Stainless Steel Overlay 
Thinline 2x6 w/ Brass Overlay 
Thinline 2x6 w/ Black Lexan
®
 Illuminated Overlay 
Thinline 2x6 w/ Braille Overlay 
* Keypad Part Number is located on the back of the Keypad 
  
KP-34S 
KP-34B 
KP-34K
 
KP-5S 
KP-5SL
 
KP-26TS 
KP-26TB 
KP-26TI 
KP-26TR
 
 
KP-5SI 
KP-5DI
 
 
5
1.  The Keypad should be 
mounted on the wall 
adjacent to the door.  
It should be on the 
same side as the door 
strike and about 4 feet 
above the floor. 
 
2.  The Control Module 
should be mounted 
inside the building 
near a power source.  
Typically the control 
module is hidden in a 
false ceiling or closet. 
The control module must be located in an environmentally 
controlled area where the temperature remains between    
  – 40
°C and +49°C (-40° F and 125° F.) 
 
 
Typical Installation 
3.  The Wiring Cable connects the keypad to the control 
module.  It is important not to locate the cable adjacent to 
any wiring that carries line voltage. Included with the 
system is a 15-foot CL2 12 conductor jacketed wiring cable 
of which only 11 wires are used.  If the Control Module 
must be located further than 15 feet from the Keypad, 
additional cable may be spliced. The maximum distance 
between the Keypad and the Control Module must not 
exceed 1,000 feet (250 feet for an Illuminated 5-Pad). For 
runs over 200 feet, 18 gauge wire should be used. Under 
200 feet, 20 gauge is acceptable. 
 
4.  The Electric Strike/Other Locking Device(not included) 
connects to the KE-265’s Main Relay output via a strike 
cable. (See Appendix B – Typical Wiring Diagrams. Page 
24)