Sapphire Audio DV425TR Benutzerhandbuch

Seite von 60
DV425TR DIRECT VENT ROOM HEATER
02/01                                                                                     Page 55                                                                               250-5533
TROUBLE SHOOTING (continued)
PROBLEM
Pilot will not Hold 
(Cont.)
Pilot Drops Out.
No gas to Main 
Burner
Thermostat/Wall 
Switch will not 
cycle the Main 
Burner.
POSSIBLE CAUSE:
Defective Magnet
(mV Plus systems).
Defective Safety Magnet
(milliVolt System)
Pilot Orifice blocked.
Wrong Pilot Orifice.
Low gas pressure to 
appliance.
Pilot not lit.
Control Knob in the "ON" 
position.
Thermostat not in the "ON" 
position.
Thermo-generator out-put 
voltage not within design 
parameters.
Defective Thermostat or 
Thermostat Wiring.
Defective Wall Switch. 
SOLUTIONS:
If the mV reading is above 6mV and the Safety Magnet does 
not hold, replace the Valve.
(E) If closed-Circuit mV reading is the same as the Open-
Circuit reading, the Coil is electrically "Open". Replace the 
Valve.
Verify operation of Safety Magnet in the following manner:
(A) Remove all Wires from the Terminals of the Main 
Operator.
(B) Measure the electrical voltage between the Termihals 
TPTH and TP.  If the voltage is above 110mV and the Safety 
Magnet does not hold, replace the Valve.
Replace Orifice with a new Orifice of the exact size and type.
Replace the Orifice with a new Orifice supplied specifically 
for the appliance and gas in question.
Check Gas Pressure (&" NG/11"LP)
Light Pilot and wait for Thermo-generator to heat up 
sufficiently to power the Main Operator.  If Pilot fails to light, 
hold, hold, refer to the above sections.
Rotate "OFF/PILOT/ON" Control Knob to the "ON" position.
Turn Thermostat "ON" and then adjust Temperature Control 
to call for heat.
If unable to meet minimum requirements, replace the 
Thermo-generator.
(A) With the apilot adjusted properly, place a Jumper Wire 
between TPTH and TH.  Take a mV reading across the TPTH 
and TH Terminals of the Valve.  This Closed Circuit voltage 
should not fall below 300mV. Record reading.
(B) Remove Jumper wire from the TPTH and TH conections 
and connect the Thermostat Wires to the same Terminals. 
Closed Circuit voltage as described in the previous Step.  If 
the mFV reading drops below 150mV, excessive resistance 
exists in the Thermostat Circuit and must be isolated and 
eliminated.
Repeat the above troubleshooting items covered under 
"Defective Thermostat or Thermostat Wiring" except, 
substitute the words "Wall Switch" where the word 
Thermostat appears in the instructions.