MAINTENANCE 
 
 
 
RECOMMENDED INSPECTION AND 
MAINTENANCE TYPES
 
 
NOTE:   Refer to the SAFETY section of this 
manual for important information.  
 
A. Acceptance Inspection 
 
  This inspection confirms that the circuit 
breaker unit is complete, correct as specified, 
and undamaged from shipment. The 
procedure for this inspection is outlined in the 
RECEIVING, INSPECTION AND HANDLING 
section of this manual. 
 
B. Patrol Inspection 
 
 
Inspection is made of the condition of the 
circuit breaker while it is energized.  Check 
that no unusual sounds or smells exist 
externally. 
 
Inspection Frequency:  Once every 6 months 
 
C. Periodic Inspection 
 
Inspection is performed with the circuit breaker 
de-energized.  The lubrication of sliding and 
rotating parts is checked and the mechanism 
is lubricated if needed. 
 
Inspection Frequency:  Once every 1-3 years 
or every 3000 operations (normal).  Once 
every 6 years (detailed). 
 
Refer to Table 2 for the schedule of Periodic 
Inspections. 
 
D. Unscheduled Inspection 
  
Inspections are implemented as required. 
 
Inspection Frequency:  As needed 
 
NOTE: 
The inspection frequency and points 
to be inspected may vary from the 
above recommendations depending 
on the status of use, frequency of 
switching, amount of current 
interrupted and other factors. 
 
 
 
 
 
 
Table 1  Tightening Torques
 
 
Screw 
Nominal 
Dia. 
 
Tightening Torque 
M4 15-20 
kgf-cm 
13-17 in-lb 
M5 30-40 
kgf-cm 
26-34 in-lb 
M6 50-65 
kgf-cm 
43-56 in-lb 
M8 120-150 
kgf-cm 
9-11 ft-lb 
M10 250-315 
kgf-cm 
18-23 ft-lb 
M12 450-565 
kgf-cm 
32-41 ft-lb 
 
 
 
 
 
 
 
 
 
 
 
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net