Toshiba 18 - 1250 A Benutzerhandbuch

Seite von 99
TE Series        
          Digital Solid State Soft Starters   18 – 1250A 
2.6.1 Power 
Terminals: 
Connection points for units of 160A and below are saddle clamps 
suitable for stranded wire. Connection points for units of 210A and 
above are bus tabs with pre-drilled holes (see below). Use appropriate 
compression or mechanical lugs for termination to these bus tabs. 
Suggested wire sizes and tightening torques for factory-supplied 
connectors when using conductors rated for 75
°C are shown in the 
chart below. Always consult local codes and industry standard practices 
for proper wires sizes to accommodate voltage drop and ambient 
conditions. 
 
Model 
Number 
Current 
Range 
Min.- Max.
Suggested
Wire Size 
AWG 
Tightening 
Torque 
in.-lbs. 
Screw / Bolt 
Size 
  
Tightening 
Torque 
Nm 
Suggested 
Wire Size 
ISOmm
2
 
TE-18-BP 
9 - 18 
12 
35 
1 x M5  
(included) 
TE-28-BP 
14 - 28 
10 
10 
TE-39-BP 
19 - 39 
16 
TE-48-BP 
24 - 48 
16 
TE-62-BP 
36 - 62 
45 
1 x M8  
(included) 
25 
TE-78-BP 
39 - 78 
35 
TE-92-BP 
46 - 92 
35 
TE-112-BP 
56 - 112 
50 
TE-150-BP 
75 - 150 
80 
1 x M8  
(included) 
70 
TE-160-BP 
80 - 160 
2/0 
70 
TE-210-BP or -P 
105 - 210 
4/0 
200 
1 x 0.38" hole 
(M10) 
for User 
supplied 
 lugs 
15 
120 
TE-276-BP or -P 
138 - 276 
300 kCMIL 
150 
TE-360-BP or -P 
180 - 360 
500 kCMIL 
300 
TE-450-BP or -P 
225 - 450 
2 x 250 kCMIL
2 x 150 
TE-550-BP or -P 
275 - 550 
2 x 250 kCMIL
2 x 150 
TE-718-BP or -P 
356 – 718 
CF CF CF CF  CF 
TE-900-BP or -P 
450 – 900 
CF CF CF CF  CF 
TE-1000-BP or -P 
50 - 1000 
CF CF CF CF  CF 
Table 2.6:  TE Series Wire Ranges and Torque Specifications 
 
 
 
 
 
CF = Consult Factory 
 
2.7 
Remote Keypad Mounting 
The keypad / operator interface unit can be remotely mounted up to 10’ 
(3 meters) away from the starter, i.e. on the enclosure door. A remote 
mounting kit is necessary, consisting of an adaptor plate, a doorframe 
for NEMA 1 or NEMA 12 enclosures and a pre-assembled ribbon cable 
available in 1-meter length increments. Detailed assembly instructions 
and an enclosure cutout template are included with that kit. See Product 
Selection Guide for part numbers of the different kits depending on 
NEMA rating and cable lengths. 
Figure 2.7  
Remote Keypad Mounting Kit 
Components 
Adaptor Plate
~
~
~
Ribbon Cable,
 
1, 2 or 3 meters
 
NEMA 1 or
NEMA 12
Door Frame
TE Starter