Toshiba 18 - 1250 A Benutzerhandbuch

Seite von 99
TE Series        
          Digital Solid State Soft Starters   18 – 1250A 
37 
F004 =  Overload Class During Run 
Factory Setting = 10 (Class 10) 
Range = 5 - 30 NEMA / UL Class
 
Set value according to the instructions provided by your motor / 
equipment manufacturer. This trip curve will not be enabled until 
the motor has reached full speed. 
 
F005 =  Overload Reset 
Factory Setting = 0 (Manual) 
Range = 0 – 2
 
Set value to determine starter behavior after an overload 
condition has cleared. 
 
When set to 0 = Manual, the operator must press the [RESET] 
key before restarting the motor. Once the motor windings have 
cooled sufficiently AND the [RESET] key is pressed, the unit 
will accept a restart command. 
 
When set to 1 = Automatic mode, and once sufficient time has 
elapsed allowing motor windings to cool, the motor will be 
restarted upon a start command. If 2-wire control is used, the 
unit will restart immediately. 
 
When set to 2 = Disabled Overload, the TE Series will not trip 
on Motor Thermal Overload. This is provided for applications 
where either an external Overload Relay or Motor Protection 
Relay is used, or where multiple motors are connected and 
each one requires having an individual Overload Relay. See 
Appendix 5 for more details. 
 
    WARNING
 
Setting F005 = 1 (Automatic) may present significant operational risk.  
When F005 = 2 (Disabled Overload), a separate external thermal overload protection device 
must be in the circuit. 
 
ƒ  NOTE: 
Because of the risk of fire or equipment damage, cycling control 
power will NOT reset an Overload Trip. If F005 = 2 (Automatic 
Reset), cycling control power will allow reset ONLY IF the Thermal 
Register has determined that the motor has regained sufficient 
thermal capacity to allow it to restart successfully. 
 
 
F006 - F009 = Reserved