F050 =  Minimum Time Between Starts Lockout 
Factory Setting = 0 (Disabled) 
Range = 1 - 60 minutes, or 0 (Disabled) 
When F050 is set to 1 through 60, the motor cannot be 
restarted within the time specified after the first start. Time 
between starts is calculated from the time of the first start 
command to the next regardless of run time or off time. 
 
Example:  
If F050 = 15, motor will not be allowed to re-start within 15 
minutes of first start. 
 
This function is useful as a “Short-Cycle Timer” in preventing 
excessive wear on motors where automatic demand control 
may occasionally cycle on and off too quickly, such as 
compressors or sump pumps 
 
 
 
ƒ  5.6.9.a  
Internal Protection Features 
The TE Series starter contains additional protection features that 
are built-into the hardware and factory preset. Function F051 is 
provided to alter these settings via numerical preset programming. 
For maximum protection, all of these features are turned On as a 
factory default and should be left that way unless changes are 
necessary for service purposes, testing or to accommodate non-
standard applications. Factory default settings are as follows: 
ƒ  Phase Rotation: Protection is ON,  
expected rotation sequence is set for A-B-C 
ƒ  Phase Current Loss (Running): Protection is ON, trips at <20% of 
unit Max amps after 3 seconds of acceleration and at full speed. 
ƒ  Shorted SCR: Protection is ON, unit will lock out if one SCR is 
shorted (no voltage drop across the SCR) 
ƒ  Shunt Trip: Protection is ON; unit trips if current flows in any phase 
while in OFF mode. 
ƒ  PTC Trip: Protection is ON; unit will trip if PTC Input resistance 
exceeds set value (or open). 
ƒ  Line Phase Loss (Stopped): Protection is ON; unit will trip if any 
line voltage is not present while the unit is not accelerating or 
stopped. 
 
F051 =  Internal Protection Features 
Factory Setting = 127 (all enabled) 
Range = 1 – 127: Numeric value representing bit locations
 
F051 represents the numeric value of a byte (8 bits) of memory 
which enables or disables these features. Each bit within that 
byte acts like a “dip switch” to alter the associated feature, but 
instead of having to open the starter case, changes can be 
done via the keypad. Each function has a fixed numeric decimal 
value associated with it. Adding or subtracting decimal values to 
this function changes the binary (On-Off) status of each bit and 
is simply done by entering the new value into F051. The Factory 
Default value is F051 = 0127, which has all features On. 
Numeric values for each feature are as follows: