Toshiba 18 - 1250 A Benutzerhandbuch

Seite von 99
TE Series        
          Digital Solid State Soft Starters   18 – 1250A 
62 
Chapter 6 - Start-up 
6.1  
Basic Startup  
Your new TE Series Soft Starter is factory preset for a wide variety of 
applications and often can be used with minimal adjustment.  
6.1.1 
Three Step Process 
1. Connect L1, L2, and L3 to power lines and  
    T1, T2, and T3 to motor. 
2. Connect control wires and control power. 
3. Program motor FLA (F001). 
6.1.2 
Start-up Parameters and Factory Defaults 
Try the initial presets first and then adjust or enable the more 
advanced features to meet your specific starting needs. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Fn # 
Function  
Name 
Factory 
Setting 
Description / Factory Setting 
F001 
Motor Nameplate 
FLA. 
FLA must be programmed for 
starter to function. 
F002 
Motor Nameplate  
Service Factor 
1.0 SF 
Change only if necessary AND 
motor is rated over 1.0SF 
F003 
Overload Class 
During Start 
Class 10 
NEMA / UL Class 10 
F004 
Overload Class 
During Run 
Class 10 
NEMA / UL Class 10 
F005 
Overload Reset 
0 (Manual) 
0 = Manual 
F010 Ramp 
Profile 
Ramp 1 and Ramp 2 =  
Voltage Ramp with Current Limit 
F011 
Initial Torque 
60 
60% Initial Voltage 
F013 
Ramp Time 
10 
10 Second Ramp (Ramp 1) 
F014 
Current Limit 
350 
350% of programmed FLA 
F015 – 
F018 
Ramp 2 settings 
--- 
Inactive unless Ramp 2 Input is 
closed 
F019 – 
F052 
Software protection 
and control 
features 
--- 
Inactive unless selected 
F053 
Internal hardware 
protection features 
127 All 
active 
F054 – 
F059 
Timer and counter 
value readouts 
--- Read 
only 
F060 
Aux Relay #1 
Run / Stop 
F061 
Aux Relay #2 
At-Speed / Stop 
F062 
Aux Relay #3 
16 
Any Trip 
F063 
Aux Relay Delay 
No Delay 
F065 – 
F068 
Communications  
---- 
Not Used unless without optional 
Comm Adaptor 
F070 
Parameter Lock 
User password disabled 
F071 
Reset Function 
Use to reset to default values 
F073 – 
F080 
System settings 
and time clock 
--- 
User choice to adjust clock 
F085 – 
F093 
Fault History 
--- 
Read only 
Table 6.1.2: Factory Presets