Toshiba TOSVERT VF-S11 Gebrauchsanleitung

Seite von 81
E6581160
52
7
Title
Communication
No.
Function
Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
E6581158
RV
0015
V/F control mode
selection
-
-
0: V/F constant
1: Variable torque
2: Automatic torque boost control
3: Vector control
4: Energy-saving
5: Dynamic energy-saving
(for fans and pumps)
6: PM motor control
2
5.11
XD
0016
Torque boost
value 1
%
0.1/0.1
0.0-30.0
* 1
5.12
VJT
0600
Motor electronic-
thermal protection
level 1
%
(A)
1/1
10-100
100
5.13
6.19.1
Setting
Overload protection
OL stall
0
{
×
1
{
{
2
×
×
3
Standard
motor
×
{
4
{
×
5
{
{
6
×
×
QNO
0017
Electronic-thermal
protection
characteristic
selection  *2
-
-
7
VF motor
×
{
0
5.13
UT
0018
Preset-speed
operation
frequency 1
Hz
0.1/0.01
NN
-WN
0.0
UT
0019
Preset-speed
operation
frequency 2
Hz
0.1/0.01
NN
-WN
0.0
UT
0020
Preset-speed
operation
frequency 3
Hz
0.1/0.01
NN
-WN
0.0
UT
0021
Preset-speed
operation
frequency 4
Hz
0.1/0.01
NN
-WN
0.0
UT
0022
Preset-speed
operation
frequency 5
Hz
0.1/0.01
NN
-WN
0.0
UT
0023
Preset-speed
operation
frequency 6
Hz
0.1/0.01
NN
-WN
0.0
UT
0024
Preset-speed
operation
frequency 7
Hz
0.1/0.01
NN
-WN
0.0
5.14
H
-
Extended
parameters
-
-
-
-
-
4.1.2
ITW
-
Automatic edit
function
-
-
-
-
-
4.1.3
*1 : Default values vary depending on the capacity. See the table of the page 64.
*2 : { : valid, 