Toshiba TOSVERT VF-S11 Gebrauchsanleitung

Seite von 81
E6581160
68
7
Q
Table of output terminal functions 2
Function
No.
Code
Function
Action
12
OT
Over-torque detection
ON: Torque current is equal to or larger than
H
 set value and longer than H
set time.
OFF: The torque current is equal to or less than
(H set value - H set value).
13
OTN
Inversion of over-torque detection
Inversion of OT
14
RUN
Start/Stop
ON: When operation frequency is output or during
(FD)
OFF: Operation stopped
15
RUNN
Inversion of RUN/STOP
Inversion of RUN setting
16
POL
OL pre-alarm
ON: 50% or more of calculated value of overload
protection level
OFF: Less than 50% of calculated value of
overload protection level
17
POLN
Inversion of OL pre-alarm
Inversion of POL setting
18
POHR
Braking resistor overload pre-alarm
ON: 50% or more of calculated value of  H
set overload protection level
OFF: Less than 50% of calculated value of
H
 set overload protection level
19
POHRN
Inversion of braking resistor overload pre-alarm
Inversion of RCHR setting
20
POT
Over-torque detection pre-alarm
ON: Torque current is equal to or larger than 70%
of H set value.
OFF: The torque current is below (H set
value x 70% - H set value).
21
POTN
Inversion of over-torque detection pre-alarm
Inversion of POT setting
22
PAL
Pre-alarm
One of the following is turned on:
ON POL, POHR, POT, MOFF, UC, OT, LL
stop, COT, and momentary power failure
slowdown stop.
or E,R,QTJ issues an alarm
All the following are turned off:
OFF POL, POHR, POT, MOFF, UC, OT, LL
stop, COT, and momentary power failure
slowdown stop.
or E,R,QTJ issues no alarm
23
PALN
Inversion of pre-alarm
Inversion of PAL setting
24
UC
Small-current detection
ON: The output current is equal to or less than
H
 set value for H set time.
OFF: The output current is equal to or larger than
H
 set value + 10%.
25
UCN
Inversion of small-current detection
Inversion of UC setting
26
HFL
Significant failure
ON:  QEC,QEN,QV,G,
GGR
,GVP,GRJQ,GTT-

,QJ,WR,GH,WE,
GV[R
,QTGRJ)
OFF: Failure other than the above
27
HFLN
Inversion of significant failure
Inversion of HFL setting
28
LFL
Insignificant failure
ON:  (QE-,QR-,QJ,
QN
-,QNT)
OFF: Failure other than the above
29
LFLN
Inversion of insignificant failure
Inversion of LFL setting
30
RDY1
Ready for operation (including ST/RUN)
ON: Ready for operation (ST and RUN are also
ON)
OFF: Others
31
RDY1N
Inversion of ready for operation (including
ST/RUN)
Inversion of RDY1 setting
32
RDY2
Ready for operation (excluding ST/RUN)
ON: Ready for operation (ST and RUN are not
ON)
OFF: Others
33
RDY2N
Inversion of ready for operation (excluding ST/RUN)
Inversion of RDY2
34
FCVIB
Frequency VIB selection
ON: VIB selected as frequency command
OFF: Terminal other than VIB selected as
frequency command