Toshiba TOSVERT VF-S11 Gebrauchsanleitung
E6581160
68
7
Q
Table of output terminal functions 2
Function
No.
Code
Function
Action
12
OT
Over-torque detection
ON: Torque current is equal to or larger than
H
set value and longer than H
set time.
OFF: The torque current is equal to or less than
(H set value - H set value).
13
OTN
Inversion of over-torque detection
Inversion of OT
14
RUN
Start/Stop
ON: When operation frequency is output or during
(FD)
OFF: Operation stopped
15
RUNN
Inversion of RUN/STOP
Inversion of RUN setting
16
POL
OL pre-alarm
ON: 50% or more of calculated value of overload
protection level
OFF: Less than 50% of calculated value of
overload protection level
17
POLN
Inversion of OL pre-alarm
Inversion of POL setting
18
POHR
Braking resistor overload pre-alarm
ON: 50% or more of calculated value of H
set overload protection level
OFF: Less than 50% of calculated value of
H
set overload protection level
19
POHRN
Inversion of braking resistor overload pre-alarm
Inversion of RCHR setting
20
POT
Over-torque detection pre-alarm
ON: Torque current is equal to or larger than 70%
of H set value.
OFF: The torque current is below (H set
value x 70% - H set value).
21
POTN
Inversion of over-torque detection pre-alarm
Inversion of POT setting
22
PAL
Pre-alarm
One of the following is turned on:
ON POL, POHR, POT, MOFF, UC, OT, LL
stop, COT, and momentary power failure
slowdown stop.
stop, COT, and momentary power failure
slowdown stop.
or E,R,QTJ issues an alarm
All the following are turned off:
OFF POL, POHR, POT, MOFF, UC, OT, LL
stop, COT, and momentary power failure
slowdown stop.
stop, COT, and momentary power failure
slowdown stop.
or E,R,QTJ issues no alarm
23
PALN
Inversion of pre-alarm
Inversion of PAL setting
24
UC
Small-current detection
ON: The output current is equal to or less than
H
set value for H set time.
OFF: The output current is equal to or larger than
H
set value + 10%.
25
UCN
Inversion of small-current detection
Inversion of UC setting
26
HFL
Significant failure
ON: QEC,QEN,QV,G,
GGR
,GVP,GRJQ,GTT-
,QJ,WR,GH,WE,
GV[R
,QTGRJ)
OFF: Failure other than the above
27
HFLN
Inversion of significant failure
Inversion of HFL setting
28
LFL
Insignificant failure
ON: (QE-,QR-,QJ,
QN
-,QNT)
OFF: Failure other than the above
29
LFLN
Inversion of insignificant failure
Inversion of LFL setting
30
RDY1
Ready for operation (including ST/RUN)
ON: Ready for operation (ST and RUN are also
ON)
OFF: Others
31
RDY1N
Inversion of ready for operation (including
ST/RUN)
ST/RUN)
Inversion of RDY1 setting
32
RDY2
Ready for operation (excluding ST/RUN)
ON: Ready for operation (ST and RUN are not
ON)
OFF: Others
33
RDY2N
Inversion of ready for operation (excluding ST/RUN)
Inversion of RDY2
34
FCVIB
Frequency VIB selection
ON: VIB selected as frequency command
OFF: Terminal other than VIB selected as
OFF: Terminal other than VIB selected as
frequency command