COMBUSTION AIR SUPPLY 
For a mobile home installation the stove must be connected to an 
outside source of combustion air. A 3” inside diameter metallic pipe, 
either flexible or rigid, may be attached to the inlet at the stove’s rear 
(refer to figures 4, 5 & 6). A rodent guard (minimum ¼” wire mesh) 
must be used at the terminus (refer to figure 5). All connections must 
be secured and airtight by either using the appropriately sized hose 
clamp and/or UL-181-AP foil tape.  
For mobile home installations only: No combustion air supply 
may exceed 10 feet. 
Sources of Outside Combustion Air 
• 
A hole in floor near stove rear terminating only in a 
ventilated crawl space. 
• 
A hole in the wall behind the stove. 
WHEN OUTSIDE AIR IS NOT USED 
If outside air is not used, it is important that combustion air be easily 
available to the air inlet. A closeable outside air register can be used 
in tightly insulated homes. 
VENTING 
The Osburn Hybrid-45 MF is certified for use with Vent type UL-103 
or ULC S629M and Chimney type UL-641 or ULC S609, 3” or 4” 
diameter in size. This unit can be installed in an existing chimney 
with the addition of a liner if it’s more than 4” in diameter.  Class “A” 
chimney is not required. Refer to the instructions provided by the 
vent or chimney manufacturer, especially when passing through a 
wall, ceiling or roof. 
This is a pressurized exhaust system. All vent connector joints must 
be sealed with 500
°F (260°C) RTV silicone sealant to ensure 
consistent performance and avoid smoke spillage. All horizontal 
connector joints must be sealed with UL-181-AP foil tape. We 
recommend that all vertical vent connector joints be secured with a 
minimum of 3 screws. 
DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING 
ANOTHER APPLIANCE. 
DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING 
SYSTEM OF THIS UNIT. 
INSTALL VENT AT CLEARANCES SPECIFIED BY THE VENT 
MANUFACTURER. 
WARNING     DO NOT INSTALL IN SLEEPING ROOM 
CAUTION     THE STRUCTURAL INTEGRITY OF THE 
MANUFACTURED HOME FLOOR, WALL, AND CEILING/ROOF 
MUST BE MAINTAINED 
 
 
 
AIR INLET
EXHAUST
 
 
 
 
 
 
TRIM
COLLAR
RODENT
GUARD
 
 
 
 
VENTILATED 
CRAWL SPACE
 
 
 
 
 
INSTALLATION
FIGURE 4 
Rear view 
FIGURE 5 
Fresh air supply 
FIGURE 6 
Fresh air supply