Omron Healthcare VARISPEEDF7 Benutzerhandbuch

Seite von 25
EN-22
OC
Over Current

Over Current
The Inverter’s output current exceeded the over-
current detection level.
• Remove the motor and run the Inverter 
without the motor. 
• Check the motor for a phase-to-phase 
short.
• Verify the accel/decel times (C1-
††
).
• Check the Inverter for a phase-to-phase 
short at the output.
OH
Heatsnk Overtemp

Heatsink Overheat 
L8-03 = 0,1 or 2 and the temperature of the 
Inverter's cooling fin exceeded the L8-02 value. 
• Check for dirt build-up on the fans or heat-
sink. 
• Reduce the ambient temperature around 
the drive.
• Replace the cooling fan(s).
Inverter's Cooling Fan Stopped

L8-03 = 3 or 4 and the temperature of the 
Inverter's cooling fin exceeded the L8-02 value. 
OH1
Heatsink Max Temp

Heatsink Overheat 
The temperature of the Inverter’s heatsink 
exceeded 105 °C.
• Check for dirt build-up on the fans or heat-
sink.
• Reduce the ambient temperature around 
the drive.
• Replace the cooling fan(s).
Inverter’s Cooling Fan Stopped
OL1
Motor Overload

Motor Overload
Detected when L1-01 is set to 1,2 or 3 and the 
Inverter’s I²t value exceeded the motor overload 
curve. 
The overload curve is adjustable using parame-
ter 
E2-01 (Motor Rated Current), L1-01 (Motor Pro-
tection Selection) and L2-02 (Motor Protection 
Time Constant)
• Recheck the cycle time and the size of the 
load as well as the accel/decel times (C1-
††
).
• Check the V/f characteristics (E1-
††
).
• Check the setting of Motor Rated Current 
Setting (E2-01).
OL2
Inv Overload

Inverter Overload
The Inverter output current exceeded the Invert-
ers’s overload capability
• Recheck the cycle time and the size of the 
load as well as the accel/decel times (C1-
††
).
• Check the V/f Characteristics (E1-
††
).
• Check if the inverter rated current matches 
the motor rated current. 
OS
Overspeed Det.

F1-03 = 0, 1 or 2 and A1-02 = 1 or 3
The motor speed feedback (U1-05) exceeded 
the setting in F1-08 for a time longer than the 
setting of 
F1-09
• Adjust the ASR settings in the C5 parame-
ter groupt
• Check the reference circuit and reference 
gain. 
• Check the settings in F1-08 and F1-09

F1-03 = 3 and A1-02 = 1 or 3
The motor speed feedback (U1-05) exceeded 
the setting in F1-08 for a time longer than the 
setting of 
F1-09
OV
DC Bus Overvolt

(only in 
stop 
condi-
tio)

The DC bus voltage has exceeded the overvolt-
age detection level.
Default detection levels are: 
200 V class: 410 VDC
400 V class: 820 VDC
• Increase the deceleration time (C1-02/04) 
or connect a braking option.
• Check the power supply and decrease the 
voltage to meet the inverter’s specifica-
tions.
• Check the braking chopper / resistor.
PF
Input Phase Loss

Input Phase Loss
Too big DC bus voltage ripple. 
Only detected when L8-05=1 (enabled)
• Tighten the input terminal screws
• Check the power supply voltage
PGO
PG Open

PG Disconnection
Detected when F1-02 = 0, 1 or 2 and A1-02 = 1 
or 3.
Detected when no PG (encoder) pulses have 
been received for a time longer than the setting 
in F1-14.
• Fix the broken/disconnected wiring.
• Supply power to the PG properly.
• Check the sequence and if the brake is 
opened when the inverter starts to increase 
the speed. 

PG Disconnection
Detected when F1-02 = 3 and A1-02 = 1 or 3.
PG (encoder) pulses have not been received for 
a time longer than the setting in F1-14.
 Display
Alarm
Fault
Meaning
Corrective Actions