Omron SYSMAC C200HW-ZW3AT2-E-V2 Benutzerhandbuch
3-3
Section
Connecting to a Node
35
0
0
0
9,600 bps
0
1
0
2,400 bps
0
1
1
4,800 bps
1
0
0
9,600 bps
1
0
1
19,200 bps
Data length
0: 7 bits
1: 8 bits
0: 7 bits
1: 8 bits
Parity
0: Even
1: Odd
0: Even
1: Odd
Parity check
0: Yes
1: No
0: Yes
1: No
Stop bits
0: 2 bits
1: 1 bit
0: 2 bits
1: 1 bit
Communications Port 2
Specify an Xoff (send stop) code.
The initial value is 13 Hex and the bit string is as follows:
The initial value is 13 Hex and the bit string is as follows:
13 Hex = 0001 0011
Specify an Xon (send stop release) code.
The initial value is 11 Hex and the bit string is as follows:
The initial value is 11 Hex and the bit string is as follows:
11 Hex = 0001 0001
Specify the transmission delay.
The initial value is 00 Hex (0 ms) and the bit string is as follows:
The initial value is 00 Hex (0 ms) and the bit string is as follows:
00 Hex = 0000 0000
Set all bits of bytes [+15] to [+19] to 0.
b7 b6 b5 b4 b3 b2 b1 b0
Byte
[+10]
b7 b6 b5
Baud rate
b7 b6 b5 b4 b3 b2 b1 b0
[+11]
0
0
0
0
0
0
Retries
0: No
1: Yes
0: No
1: Yes
Communications mode
0: Full duplex
1: Half duplex
0: Full duplex
1: Half duplex
Xon/Xoff control:
0: No
1: Yes
0: No
1: Yes
b7 b6 b5 b4 b3 b2 b1 b0
[+12]
b7 b6 b5 b4 b3 b2 b1 b0
[+13]
b7 b6 b5 b4 b3 b2 b1 b0
[+14]
CQM1H PCs
Connecting to Peripheral Port
Use one of the following methods when connecting to the peripheral port on the
CPU Unit.
Use one of the following methods when connecting to the peripheral port on the
CPU Unit.
a) Set DIP switch pins 5 and 7 to ON, and set the baud rate for the Controller
Link Support Software to 9,600 bps.