Power OFF Operation
Section 4-4
Note
The above timing chart shows an example when the User-set Power OFF
Detection Time is set to 0 ms.
The following timing chart shows the Coordinator Module power OFF opera-
tion in more detail.
Power OFF Timing Chart
Fixed Power OFF Detection Time
The time it takes to detect power OFF after the power supply falls below 85%
of the minimum rated voltage.
User-set Power OFF Detection Time
The time after power OFF is detected until it is confirmed. This can be set in
the System Setup within a range from 0 to 10 ms (default: 0 ms). 
If an unstable power supply is causing power interruptions, set a longer User-
set Power OFF Detection Time (10 ms max.) in the System Setup.
Power Holding Time
The maximum amount of time (fixed at 10 ms) that 5 V will be held internally
after power interruption is detected. 
10 ms
25 ms
25 ms
0
0 to 10 ms
Time
10 to 25 ms
Power supply 
voltage
Power supply 
voltage
Power supply 
voltage
Momentary power 
interruption not detected 
and operation continues.
85% of the rated voltage or less
Operation will continue or stop 
depending on whether or not a 
momentary power interruption 
is detected.
Momentary power 
interruption detected 
and operation stops.
Reset signal
Stopped
Fixed Power OFF 
Detection Time: 
Default is 10 to 
25 ms (Power OFF 
undetermined)
Holding time for 5 V internal 
power supply after power 
OFF detection: 10 ms.
Power OFF detected
Power OFF confirmed
User-set Power 
OFF Detection 
Time: 0 to 10 ms 
(set in System 
Setup)
Operation always stopped at this 
point regardless.
Processing time after 
power OFF is confirmed: 
10 ms minus User-set 
Power OFF Detection 
Time 
Note: The interrupt task 
execution time must be 
less than or equal to pro-
cessing time after power 
OFF is confirmed.
85% of rated 
voltage
Power OFF 
detected signal
Program execution 
status
Cyclic task or interrupt tasks not associated with power OFF