Jotul GZ 550 DV II Benutzerhandbuch

Seite von 32
11
9
12
Height in Feet
From V
ent Collar
Horizontal Run in Feet
Max. One 90°
Elbow
3
5
5
10
12
Figure 15.  Horizontal termination -5/8 pipe.
Figure 16. Horizontal Termination - 4/6 Pipe.
Minimum 1 ft. rise required.
9
12
Height in Feet
From V
ent Collar
Horizontal Run in Feet
Max. One 90°
Elbow
3
5
5
10
12
1
Figure 17.  Vent Terminal Clearances - National Fuel Gas Code.
Horizontal Termination Clearance
A = Clearance above grade, veranda, porch , deck, or
balcony : *12 inches (30 cm) minimum.
B = Clearance to window or door that may be opened:
Min. 9 inches, U.S. /  *12 inches (30 cm) CAN.
We recommend 12in. minimum to prevent condensa-
tion on the window.
C = Clearance to permanently closed window:
Min. 9 inches, U.S. /  *12 inches (30 cm) CAN
We recommend 12in. minimum to prevent condensa-
tion on the window.
D = Vertical clearance to ventilated soffit located above
the terminal within a horizontal distance of 2 feet (60 cm)
from the centerline of the terminal: 18 inches
(46 cm) minimum.
= Clearance to unventilated soffit:  *12 inches (46 cm)
minimum.
= Clearance to outside corner: Min. 9 inches, U.S. /  *12
inches (30 cm) CAN. We strongly recommend 12 inches,
particularly where windy conditions pevail.
G = Clearance to inside corner:  Min. 6 inches, U.S. /  *12
inches (30 cm) CAN. We strongly recommend 12 inches,
particularly where windy conditions pevail.
H = *Not to be installed above a meter/regulator assembly
within 3 feet (90 cm) horizontally from the center-line
of the regulator.
I = Clearance to service regulator vent outlet:
3 feet, U.S.   / 6 feet (1.8 m), CAN.
= Clearance to nonmechanical air supply inlet to building
or the combustion air inlet to any other appliance:
*12 inches (30 cm) minimum.
= Clearance to a mechanical air supply inlet: *6 feet
(1.8 m) minimum.
L = ** Clearance above paved sidewalk or a paved driveway
located on public property: *7 feet (2.1 m) min.
M = Clearance under veranda, porch, deck, or balcony:
*12 inches (30 cm) minimum.
 1
* As specified in CGA B149 Installation Codes. Note: Local Codes
and Regulations may require different clearances.
** A vent shall not terminate directly above a sidewalk or driveway
which is located between two single family dwellings and serves
both dwellings.*
1
Only permitted if veranda, porch, deck, or balcony, is fully open
on a minimum of two sides beneath the floor.*