Motorola GT10 Benutzerhandbuch

Seite von 195
GT10/GT30
4.5 Connecting the FP2/FP2SH CCU
51
4.5
Connecting the FP2/FP2SH CCU
AIP81842D
GT30
FP2 computer communication unit
GT10
DIP switch settings on reverse side of FP2 computer communication unit
SW No.
Setting contents
Value Set
Switch status
1
Reserved for system
ON
2
COM.1 transfer speed
19200 bits/s ON
3
p
OFF
4
COM.1 data length
8 bits
ON
5
Reserved for system
ON
6
COM.2 transfer speed
19200 bits/s ON
7
p
OFF
8
COM.2 data length
8 bits
ON
With the FP2 CCU, the parity check is fixed at “Odd”, and the number of stop bits is fixed at “1 bit”.
PLC communication cable: D–sub 9–pin loose–wire cable (AIP81842D)
1
2
3
4
5
6
7
8
9
Signals on D–sub side
Pin no.
Wire color
GT COM port
1
––
––
2
White
RD
3
Green
SD
4
––
5
––
6
––
––
7
Brown
GND
8
––
––
9
––
––
Specifications
Length
Product no.
D–sub 9–pin 
Single–side
loose wiring
AIP81842D
2m
5mm
35mm
2000mm
Wires’ cross section: 0.25mm
2
Connecting to the FP2 computer communication unit (CCU)
1
FG
SD
RS
SG
CS
RD
2
3
4
5
6
N.C.
7
8
9
N.C.
ER
SD
SD
RD
CS
GND
RS
RD
RS
CS
GND
1
2
3
4
5
6
7
8
9
GT10/GT30
Pin no. on PLC side
No. 3 (green)
No. 2 (white)
No. 7 (brown)
PLC side
GT main unit side
Pin no.
Pin no. Abbreviation
Abbreviation
If both serial ports of the
FP2 computer commu-
nication unit are being
used, each port should be
set individually as shown
at the left.