While the oil burner is adjusted at the factory, it is re-
commended that the operating characteristics of the
burner be determined at start-up and readjusted if
necessary. Run the unit long enough at the burner
maximum firing rate to make sure the burner has
reached a stable maximum operating temperature.
THEN, check the burner and adjust as follows:
commended that the operating characteristics of the
burner be determined at start-up and readjusted if
necessary. Run the unit long enough at the burner
maximum firing rate to make sure the burner has
reached a stable maximum operating temperature.
THEN, check the burner and adjust as follows:
Check to determine that the smoke spot number
does not exceed 0.5 with a Bacharach control. Ad-
just the burner as required to achieve this maximum.
does not exceed 0.5 with a Bacharach control. Ad-
just the burner as required to achieve this maximum.
Check to determine that the CO2 rate is from 12 - 13
percent and that there is no CO production. Adjust
the burner as required to achieve this operating cha-
racteristic.
percent and that there is no CO production. Adjust
the burner as required to achieve this operating cha-
racteristic.
Measure the temperature of the flue gas exiting the
unit to determine that it does not exceed 250 de-
grees F (120 C).
unit to determine that it does not exceed 250 de-
grees F (120 C).
Combustion inspection can be carried out on the
unit through the hole (item N) provided in the inspec-
tion port (item 7). Be sure to replace the washer
(item M) and the test point screw (item 6) properly
after inspection.
unit through the hole (item N) provided in the inspec-
tion port (item 7). Be sure to replace the washer
(item M) and the test point screw (item 6) properly
after inspection.
&+(&.,1*7+(6$)(7<'(9,&(6
At the time of start-up, check the safety and control
devices as follows :
devices as follows :
- Thermostats :
• Check to see that the thermostat bulbs are
correctly positioned in their housings. This is
essential to provide temperature sensing to
facilitate burner shut-down in the event of
overheating,
essential to provide temperature sensing to
facilitate burner shut-down in the event of
overheating,
- Flame monitoring :
• Check to make sure that the burner shuts
down properly upon the deactivation or discon-
nection of the flame monitoring device or inter-
ruption of the flow of fuel,
nection of the flame monitoring device or inter-
ruption of the flow of fuel,
- Safety Pressure Relief valve :
• Check the safety pressure relief valve in the
heating circuit for proper operation.