7.3 Examples of Multi UPS configurations
Electrical drawing
Description
" Minimal number
of necessary
UPSs"
2 UPSs of 1000 VA in parallel through a Static Transfer
Switch
1 UPS loaded at 75 %
1 UPS loaded at 0%
Switch
1 UPS loaded at 75 %
1 UPS loaded at 0%
1
2 UPSs of 1500 VA and a server with redundant power
supply
Each UPS loaded at 25 %
supply
Each UPS loaded at 25 %
1
2 UPSs of 1500 VA and a server with redundant power
supply
Each UPS loaded at 60 %
supply
Each UPS loaded at 60 %
2
2 UPSs of 3000 VA in hot standby configuration
1 UPS loaded at 33 %
1 UPS loaded at 0%
1 UPS loaded at 33 %
1 UPS loaded at 0%
1
2 UPSs 30 KVA parallel/ redundant mode
Each UPS loaded at 40 %
Each UPS loaded at 40 %
1
2 UPSs 30 KVA parallel/power extension mode
Each UPS loaded at 60 %
Each UPS loaded at 60 %
2
4 UPSs 100 KVA parallel
(3 power extension + 1 redundant mode)
Each UPS loaded at 70 %
(3 power extension + 1 redundant mode)
Each UPS loaded at 70 %
3
8 UPSs 400 KVA parallel
(7 power extension + 1 r redundant mode)
Each UPS loaded at 80 %
(7 power extension + 1 r redundant mode)
Each UPS loaded at 80 %
7