HP Performance Optimized Data Center (POD) 40cp Benutzerhandbuch

Seite von 63
 
Power management  34 
The high density HP POD includes an additional electrical busway in the center of the unit. 
 
 
High density HP POD 
Feature Specification 
Number of busways 
Frequency 60Hz 
Amps (per breaker) 
400A 
Neutral Ampacity (per breaker) 
480A 
Amps derated percentage 
20% 
Max usable amps (per busway) 
320A 
Voltage (per busway) 
415V 
Grounding Aluminum 
casing 
Phases 3 
 
 
Rack power 
Power is provided to each of the rack by PDUs. The PDUs can be moved around the HP POD to support 
component power requirements. The PDUs are powered by the drop boxes attached to each electrical 
busway.  
For more information regarding power shortages to the PDUs or electrical busway drop boxes, see 
Troubleshooting (on page