Power management  38 
Armed mode—Pressing a red EPO button on the POD causes the following events: 
 
The red System Alarm/EPO Shutdown light on the EPO panel illuminates to indicate that an EPO 
switch has been activated. (This light remains illuminated until all EPO buttons are restored to their 
normal state by means of a key release mechanism, and the Reset button on the EPO panel is 
pressed.) 
 
The EPO activated relay is energized and sends a signal to the EPO panel to energize the 
associated control relays. 
 
The control relays within the EPO panel shut down the affected circuit breakers in the POD. 
Test mode—All associated EPO functions are disabled, and the amber System Test Mode light on the EPO 
panel is illuminated. This mode enables the EPO buttons to be tested without removing power to the POD. 
When an EPO button is pressed, the EPO Activated relay is energized, and it energizes the associated 
control relays in the EPO panel. Although the EPO functions are disabled, the horn and strobe alarm are 
activated. To silence the alarm, press the Reset button on the EPO panel. 
Bypass mode—All EPO functions and test functions are disabled. When the EPO panel is operating in this 
mode, the green EPO Bypass light on the EPO panel is illuminated. 
 
EPMS panel 
The electric power managing system (EPMS) is composed of 120V, Nema 515R rated auxiliary power. 
The panel optionally provides additional power for auxiliary components, mainly the BMS. 
 
If you connect land power to this panel, the BMS is powered by external land power. 
 
If you do not connect land power to this panel, the BMS is powered by the House panel. 
 
Fan control panel 
The Fan Control panel houses the relay system that controls the fan speeds within the HP POD, based on 
maintaining the cold aisle temperature set through the BMS. 
You do not have to access to the Fan Control panel, and no interface setting is required. 
 
Fire alarm control panel 
If you connect your central fire alarm system to the fire alarm control panel, any emergency alarm can be 
sent directly over your facility alarm system. 
For more information about the fire alarm control panel, see the product documentation included in the 
Operations & Maintenance Guide
 
House panel 
The House panel is a 120A panel board that provides power and electrical requirements to all auxiliary 
HP POD components. 
If a breaker is tripped open, you can access to the outside of the House panel and reset the breakers. You 
can also reset the HP POD components after an EPO alarm. If one or more breakers continually trip, 
contact HP ("
The standard panel schedule resides inside the panel breaker box and can be referenced when 
necessary.