Troubleshooting 49 
Troubleshooting 
HP POD troubleshooting 
 
Issue Resolution 
The water is not flowing, or flowing too 
slowly. 
Verify that all applicable valves are open. Inspect the water 
lines for blockage, unblock, or replace them as necessary. 
The HP POD is overheating. 
If the fan is not functioning, check the integrity of the electrical 
connection to the fan. If the electrical connection seems OK, 
replace the fan.  
If the fan is functioning, check for a kink or blockage in the 
water line to the heat exchanger. 
Contact HP service. 
The strobe lights are flashing. 
Either the EPO or the fire alarm system has been activated. Get 
out of the HP POD immediately and follow standard emergency 
procedures for your facility. 
There is a leak inside the HP POD. 
Locate and note the source of the leak. Prevent the leaking 
water from contacting any electrical equipment. Repair the leak 
as soon as possible. 
There is no power to one rack. 
Verify that the racks on either side of the rack have power.  
Check the status of the busway dropbox for that rack. 
 
If a breaker has tripped, reset the breaker box and verify 
that power has been restored to the rack. 
 
If none of the busway dropbox breakers has tripped, check 
the status of the PDUs for the rack. If the input or output 
breakers have tripped, reset the PDU and verify that power 
has been restored to the rack. 
 
If none of the breakers on the busway dropbox or PDUs 
have tripped, replace the busway dropbox. 
 
There is no power to multiple racks. 
Verify that the HP POD is receiving power. 
Check the status of each of the electrical busway panels. If 
one of the breakers has tripped, reset the breaker and verify 
that power has been restored to the racks. 
Check the status of the connection transformer and 
switchboard. If one of the breakers has tripped, reset the 
breaker and verify that power has been restored to the 
racks. 
 
There is no power to the HP POD. 
Check the status of the connection transformer and switchboard. 
If one of the breakers has tripped, reset the breaker and verify 
that power has been restored to the HP POD.